Dri-Eaz LGR 7000XLi Manual Para El Usuario página 10

Ocultar thumbs Ver también para LGR 7000XLi:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Inspect the vertical condenser (hot) coil. If dust is present,
vacuum or use compressed air on both sides of the coil until it
is clean. Take care not to bend or damage the fins. Vacuum
the outside (shown) and inside surface of the vertical coil.
NOTICE: Do not use coil cleaning solution on the vertical
condenser coil. The solution may drip on to sensitive internal
components and damage them.
The horizontal evaporator (cold) coil (not shown) should
also be vacuumed. For more thorough cleaning, remove the
back cover and use coil cleaner.
Clean the horizontal evaporator (cold) coil. Use a
vacuum or condenser coil cleaner. If using the coil cleaner,
use a small container to capture runoff from the drain basin.
Note: Use Dri-Eaz Coil Cleaner only.
CAUTION: Be sure to thoroughly flush coil cleaner from
coils to avoid damaging the pump and/or pump valve.
Reinstalling the Heat Block and Top Cover
NOTICE: Be sure housing bolts are properly threaded before tightening. Do not overtighten. Do not use a power
tool!
Reinstall the heat exchange block. Be sure to position it in
the original orientation.
Carefully reseat the heat exchange block. Make sure that
the block is flush against the base and vertical condenser (hot)
coil,
Make sure the top of the block is flush with the top of the
condenser coil.
07-01776F 2015-02 F412 (115V) Warranty 07-00420
10
Dri-Eaz Products, Inc.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

F412F412-115v

Tabla de contenido