10. Specifications
10-1. Product functions
• This controller can control up to 50 air conditioners and LOSSNAY with a daily schedule either
collectively or in groups.
• This controller has only a schedule setting function and must be used with another system
controller. When used independently, only the air conditioner's ON/OFF status and error status
will be monitored (operation status display). In addition to schedule setting, the units can be
turned ON/OFF and stopped and the timer can be reset either collectively or in groups with switch
operations.
The details of the functions are listed below.
<List of system remote controller functions>
Function
Operation
Timer
Normal
functions
Monitor
ON/OFF status (*5)
Operation
Interlocked unit setting
controller/Slave system
Operation prohibit setting
Default
setting
Celsius/Fahrenheit display Set the set temperature display to a Celsius or Fahrenheit display.
function
System
(*3)
System remote control own
Indoor unit, LOSSNAY
Number of indoor units and
LOSSNAY in one group
Number of local remote
controls in one group
Number of
System
registered
limits
units
controllers that can be
controlled by one group (*2)
Number of indoor units
interlocked with one
(*1) Refer to page 30.
(*2) This controller (schedule timer) is one of the system controllers.
(*3) Refer to page 28.
(*4) Check the operation status (operation mode, set temperature, etc.) of other air conditioners with the system
controller being used.
(*5) These displayed details are the schedule setting details. These are not the air conditioner operation status
monitor details.
ON/OFF
ON/OFF operations can be carried out collectively or for each group.
Timer reset (*4)
The timer setting details can be disabled collectively.
ON/OFF
COOL/HEAT
Setting details
Room temperature adjustment (TEMP.)
Operation prohibit (ON/OFF, operation mode, setting temperature)
Number of setting patterns: 9
(Operation for a week can be set by selecting one of nine patterns for each
Number of settings
day.)
Number of operations: Up to 16 operations can be set in one pattern.
Time setting unit
The item can be set in five-minute units.
Time
The current time and day can be displayed.
Error
The address of the faulty unit and the error code are displayed on the LCD.
The ON/OFF status of the unit is displayed on the LCD when GROUP is
selected.
Set the unit (indoor unit, LOSSNAY, remote controller, slave system
Group setting
controller) group.
Set the LOSSNAY and indoor unit interlock.
Master system
Set the master and slave system controllers.
controller (*1)
Set whether to prohibit operation with the local remote control using this
Enable/disable
controller or with another controller.
To prohibit an operation, set whether to prohibit only the remote controller or
Prohibit range
to also prohibit the other controllers.
Set the schedule timer's address (Refer to the Installation Manual.)
address
Emergency stop level input, ON/OFF level input, ON/OFF and operation
External input
prohibit/enable pulse input
External output
ON/OFF status output, error/normal state output
Maximum 50 units
1 to 16 units (The indoor unit and LOSSNAY cannot be registered in the same
group.)
0 to 2 units
0 to 4 units (Note that this includes the number of local remote controllers
Number of system
used in one group)
0 to 3 units in a group having one local remote controller
0 to 16 units
LOSSNAY
Details