Before performing the installation, verify the diaphragm
to be used and make sure it does not exceed the maxi-
mum permitted length by making a simple calculation:
1. Design the entire separate flue system, including the
accessories and outlet terminals.
2. See Table 1 and determine the losses in meq (equi-
valent meters) for each component, depending on its
assembly position.
3. Make sure the total sum of the losses is less than or
equal to the maximum length indicated on Table 2 (see
section 2.7.4).
Table 1
0.5 m M/H
PIPE
1 m M/H
2 m M/H
45° H/H
45° M/H
CURVE
90° H/H
90° M/H
90° M/H + outlet for testing
Ø 80
With outlet for testing
HOSE
For condensate discharge
T
For condensate discharge
Wall air
TERMINAL
Wall fumes with wind screen
Separate for air/fumes 80/80
FLUE
Only exhaust vent Ø 80
2.7.1 Diaphragm
For the unit to operate correctly, the included diaphragms
must be installed. Make sure the correct diaphragm
has been installed (when used), and that it's properly
installed.
1
2
fig. 11 - Replacing the diaphragm with the unit disassembled
2.7.2 Condensate collection accessories (optional)
For vertical pipe installations, type C3x, C5x, B2x,
and C1x , it is advisable to install the condensate
collection accessory.
Losses in m
eq
Flue gas outlet
Air inlet
Vertical Horizontal
1KWMA38A
0.5
0.5
1
1KWMA83A
1
1
2
1KWMA06K
2
2
4
1KWMA01K
1.2
2.2
1KWMA65A
1.2
2.2
1KWMA02K
2
3
1KWMA82A
1.5
2.5
1KWMA70U
1.5
2.5
1KWMA16U
0.2
0.2
1KWMA55U
-
3
1KWMA05K
-
7
1KWMA85A
2
-
1KWMA86A
-
5
1KWMA84U
-
12
1KWMA83U+
-
4
1KWMA86U
• [1] F lue gas gasket
• [2] D iaphragm
cod. 3541S170 - Rev. 02 - 06/2019
• For connection to a Ø60/100 coaxial pipe with conden-
sate collection (010023X0).
• For connection to separate Ø80 pipes, vertical pipe
with condensate collection (1KWMA5500).
2.7.3 Connection with coaxial pipes
C1x - Horizontal aspiration and evacuation on the wall
C3x - Vertical aspiration and evacuation on the ceiling
= Air
= Flue gases
fig. 12 - Example of a connection with coaxial pipes
Maximum permitted length
Elbow reduction factor 90°
Curve reduction factor 45°
Diaphragm to be used
Ø
m SKY ECO F 7 SKY ECO F 10 SKY ECO F 12 SKY ECO F 14
0-2
Ø 34
Ø 40
60/100
2-3
Ø 35
Ø 43
3-4
Ø 36
0-3
Ø 34
Ø 40
80/125
3-6
Ø 35
Ø 43
6-10
Ø 36
Coaxial 60/100
Coaxial 80/125
4 m
10 m
1 m
0,5 m
0,5 m
0,25 m
SKY ECO F 17
Ø 40
Ø 47
Ø 50
Ø 43
Ø 50
Ø 52
NO DIAPHRAGM
Ø 43
Ø 47
Ø 50
Ø 47
Ø 50
Ø 52
NO DIAPHRAGM
EN
85