3.5 Parameters
3.5.1 Configuration Menu
Press the On/Off button for 20 seconds to access the
configuration Menu.
7 parameters are available, indicated by the letter "b".
Press the On/Off button to scroll the list of parameters,
in increasing order.
Press the DHW buttons to view or modify the value of a
parameter: the change will be automatically saved.
Description
Range
Contents
0 = Natural gas (G20)
Gas type
b01
1 = LPG (G30 - G31)
selection
2 = Propane air (G230)
Unit type
b02
1 = Water heater
selection
0 = Sealed Chamber com-
bustion control (without fume
pressure switch)
Combustion
1 = Open Chamber (with fume
chamber
b03
thermostat)
type
2 = Sealed Chamber (with
selection
fume pressure switch)
3 = Sealed, Comb. Control +
LOW_NOX
0 = 10 - 12 liters
Exchanger type
1 = 14 liters
b04
selection
2 = 17 liters
3 = 7 liters
Auxiliary relay
0 = External gas valve
b05
card operation
1 = Solar 3-way
selection (b02=1)
Mains Voltage
0 = 50Hz
b06
Frequency
1 = 60Hz
Frost protection
b07
burner on time
0-20 seconds
(b02=1)
Notes:
Parameters with more than one description vary their
function and/or range in relation to the setting of the pa-
rameter given in brackets.
Parameters with more than one description are reset to
the default value if the parameter given in brackets is
modified.
To exit the configuration Menu press the On/Off button
for 20 seconds, or exiting occurs automatically after 2
minutes.
92
EN
3.5.2 Service Menu
The card Service Menu is accessed by pressing the Re-
set button for 20 seconds. 4 submenus are available:
press the On/Off button to select, in increasing order,
"tS", "In", "Hi" or "rE".
"tS" = Transparent Parameters Menu,
"In" = Information Menu,
"Hi" = History Menu: once the submenu is selected,
press the Reset button to access it;
"rE" = History Menu Reset: see description.
Default
"tS" - Transparent Parameters Menu
14 parameters are available, indicated by the letter "P".
0
Press the On/Off button to scroll the list of parameters
in increasing order. Press the DHW buttons to view or
1
modify the value of a parameter: the change will be au-
tomatically saved.
Contents Description
P01
Ignition ramp Offset
3
Burner shutdown in
P02
DHW (b02=1)
DHW user max. setpoint
P03
(b02=1)
Anti-inertia function
P04
1
temperature (b02=1)
Anti-inertia function
P05
Post-Ventilation (b02=1)
0
P06
DHW maximum power
0 = 50Hz
P07
Absolute min. power
5
P08
Post-Ventilation
seconds
CO2 limit Offset
(b03=0 - b03=3)
P09
No effect on adjustment
(b03=1 - b03=2)
Exchanger protection
P10
intervention
Fan rpm at maximum
P11
power
Fan rpm at minimum
P12
power
P13
Fan rpm at startup
Enable manual
P14
rpm change from Tsp
cod. 3541S170 - Rev. 02 - 06/2019
SKY ECO F
Range
Default
0 ÷ 40
20
0 = Fixed
1 = Linked to setpoint
0=
2 = Solar
Fixed
3 = Not used
4 = Not used
50-65°C
50°C
70-85°C
70°C
0-5 (0=Off, 1=5 seconds,
0=Off
5=25 seconds)
7 Liters = 100%
10 Liters = 90%
0-100%
12 Liters = 100%
14 Liters = 100%
17 Liters = 100%
0-100%
0%
0=default,
0=
1=50 seconds
default
0 (Minimum) ÷ 30 (Maxi-
15
mum)
--
15
0 = NO F43
1 ÷ 25 (Example 15= 15°/
25
sec)
50 ÷ 250
200
Example
200 = 2500 rpm
190 = 2400 rpm
80 ÷ 180
Example
80 = 800 rpm
120
180 = 1800 rpm
120=1200rpm)
80 ÷ 180
Example
80 = 800 rpm,
140
180 = 1800 rpm
140=1400rpm)
0 = enabled
0
1 = disabled