FR302DPU 110 VAC Wiring
Factory Wiring
Field Wiring
NOTE: Only wiring for the
barrier passes through the
Explosion Proof Junction Box
on FR302PH models. Wiring
for the barrier is 110VAC
ONLY! Wiring the barrier
to 220VAC will damage the
barrier and meter!
Wiring for the motor (110 VAC
and 230 VAC) runs through
the junction box on the motor
(see access information on
page 11 and 13).
FR302DPU Motor Wiring (110 VAC and 220 VAC)
The 300 series pump located inside the FR302PH
Dispenser Cabinet can be wired to operate on 110 VAC
or 220 VAC. Be certain to set the Voltage Selector Switch
to the correct setting for the input voltage. The Voltage
Selector Switch is located on the end of the pump, just
above the pump wiring junction box (see illustration
below). Power should be supplied by a dedicated 30 amp
breaker.
13
Voltage Selector
Switch
Motor Wiring