INSTALLATION INSTRUCTIONS
Mounting on a round (or square) box
Warnings for KNX/EIB installations
1. The length of the bus line between the Easy thermostat and the power supply unit must
not exceed 350 metres.
2. The length of the bus line between the Easy thermostat and the most distant KNX/EIB
device must not exceed 700 metres.
3. If possible do not create ring circuits so as to prevent undesirable signals and
overloads.
4. Keep a distance of at least 4mm between the individually insulated cables of the bus
line and those of the electric line.
5. Do not damage the electrical continuity conductor of the shielding.
Bus
Shield
U P
U P
≥ 4 mm
Bus cable
Electrical continuity
conductor
56
230 V