Installation Of The Outdoor Unit; Refrigerant Piping - McQuay SLC Serie Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 61
Semi-Enclose Mounting
In case the unit is to be half-recessed into a false ceiling, please check that the unit is well-aligned.
Provide the installation space as shown in Figure D.
Figure D
The outdoor unit must be installed in such a way, so as to
prevent short circuit of the hot discharged air or obstruction
to the smooth air flow. Please follow the installation
clearance shown in the figure. Select the coolest possible
place where intake air temperature is not greater than the
outside air temperature (maximum 45°C).
Installation Clearance
Dimension
A
Minimum Distance
300
mm (inch)
(11.81) (39.37) (11.81) (19.69)
NOTE : If there is any obstacle higher than 2m, or if there
is any obstruction at the upper part of the unit,
please allow more space than the figure indicated
in the above table.
Maximum Pipe Length And Maximum Number Of Bends
If the pipe length is too long, both the capacity and the
reliability of the unit will decrease. As the number of bends
increases, resistance of the piping system to the refrigerant
flow increases and thus lowering the capacity, as a result
the compressor may become defective. See Figure O and
Figure P.
Figure O
Outdoor Unit
Ceiling Board

INSTALLATION OF THE OUTDOOR UNIT

B
C
D
1000
300
500

REFRIGERANT PIPING

Indoor Unit
1-5
10.0mm (0.39)
Top Panel Of Unit
10.0mm (0.39)
Therefore, always select the shortest path for the piping system
and follow the recommendations as tabulated in the table.
Model
Maximum Length m (feet)
15(49) 15(49) 35(114.8) 35(114.8) 35(114.8)
Maximum Elevation m (feet)
8(26.2) 8(26.2) 10(32.8) 10(32.8) 10(32.8)
Maximum Number of Bends
Figure P
20
25
30
40
50
10
10
10
10
10
Indoor Unit

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sl30cSl40cSl50cSl30crSl40crSl50cr

Tabla de contenido