04: ECO enable/disable
Interface
05: ECO voltage range setting
Interface
06: ECO voltage range setting
Interface
07: Bypass enable/disable when UPS is off
Interface
08: Bypass voltage range setting
Interface
Setting
Parameter 2: Enable or disable ECO function. You may choose
the following two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
Setting
ENA: Advanced ECO mode enable
DIS: Advanc ed ECO mode disable (Default)
Setting
Parameter 1 & 2: Set the acceptable high voltage point and low
voltage point for ECO & AECO mode by pressing Down key or Up
key.
HS: High loss voltage in ECO & AECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage. (Default:
+12V)
For 100/110/115/120/127 VAC models, the setting range in
parameter 3 is from +3V to +12V of the nominal voltage.
(Default: +6V)
LS: Low loss voltage in ECO & AECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage.
(Default: -12V)
For 100/110/115/120/127 VAC models, the setting voltage in
parameter 3 is from -3V to -12V of the nominal voltage.
(Default: -6V)
Setting
Parameter2: Enable or disable Bypass function. You may choose
the following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
Setting
Parameter 1 & 2: Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing the
Down key or Up key.
HS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from 230Vac
to 264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-140: setting the high voltage point in parameter 3 from 120Vac
to 132Vac. (Default:132Vac)
14