EN
09: Bypass frequency range setting
Interface
10: Programmable outlets enable/disable
Interface
11: Programmable outlets setting
Interface
12: Autonomy limitation setting
Interface
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from 170Vac
to 220Vac (Default:170Vac)
For 100/110/115/120/127 VAC models:
85-115: setting the low voltage point in parameter 3 from 85Vac to
115Vac. (Default:85Vac)
Setting
Parameter 1 & 2:Set the acceptable high frequency point and
acceptable low frequency point for Bypass mode by pressing the
Down key or Up key.
HS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: setting the frequency low loss point from 51Hz to
55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: setting the frequency low loss point from 61Hz to
65Hz(Default: 63.0Hz)
LS: Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: setting the frequency low loss point from 45Hz to
49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: setting the frequency low loss point from 55Hz to
59Hz(Default: 57.0Hz)
Setting
Parameter 2: Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)
Setting
Parameter 2: Set up backup time limits for programmable
outlets.
0-999: setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode. (Default: 999)
Setting
Parameter 2: Set up backup time on battery mode for general
outlets.
0-999: setting the backup time in minutes from 0-999 for general
outlets on battery mode.
DIS: Disable the autonomy limitation and the backup time will
depend on battery capacity. (Default)
Note: When setting as "0", the backup time will be only 10 seconds.
15