13: Battery total AH setting
Interface
14: Charger maximum current setting
Interface
15: Charger Boost voltage setting
Interface
16: Charger Float voltage setting
Interface
00: Exit setting
Interface
Setting
Parameter 2: Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH. Please
set the correct battery total capacity if external battery bank is
connected.
Setting
Parameter 2: Set up the charger maximum current.
1/2/4/6/8: setting the charger maximum current 1/2/4/6/8 in
Ampere. (Default: 8A)
Note: the setting is only effective for super charger
2/3/4: setting the charger maximum current 2/3/4 in Ampere.
Note: effective for standard model with additional charger installed.
Setting
Parameter 2: Set up the charger boost voltage.
225-240: setting the charger boost voltage from 225 to 240(unit:
0.01V/cell). (Default: 236)
Setting
Parameter 2: Set up the charger float voltage.
220-233: setting the charger float voltage from 220 to 233(unit:
0.01V/cell). (Default:228)
Setting
Exit the setting mode.
16
EN