Flue Exhaust Installation - LAMBORGHINI VELA X N 24 MBS/IT Manual Para La Instalación Y El Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

FLUE EXHAUST INSTALLATION

CONCENTRIC FLUE PIPE
Fit the concentric elbow pipe positioning it on the desired direction and insert on it the sealing gasket. Then fit
the appropriate diaphragm (see table below).
Fit the air intake and flue exhaust pipes, observing the distances indicated on the installation scheme. The flue
pipe should slope slightly outward.
100
Max. 3000
DOUBLE FLUE PIPE
Air
diaphragm
195
** Air intake Ø 80
ATTENTION: Use only air intake/ fume evacuation kits produced by Lamborghini Caloreclima.
94,5
100
600
VELA X N 24
Maximum length of CONCENTRIC FLUE PIPE 3 m
Maximum length of DOUBLE FLUE PIPE
(Intake + Exhaust) 20 m VELA X N 24
Installing an elbow to connect the boiler to the chimney will cause a
drop in pressure.
The values set out in the table below indicate the necessary
modifications to the length of the linear pipes.
Max. 3000
222
440
CONCENTRIC FLUE PIPE
Max. length
Over 1 m
1 m
Diaphr.
Diaphr.
Ø 77 mm
Ø 88 mm
TYPE OF INSTALLATION
Concentric flue pipe
Separate intake/exhaust
DOUBLE FLUE PIPE
from 0,5 to 10 m from 10 to 20 m
Diaphr.
Diaphr.
Ø 48 mm
Ø 44 mm
ELBOW FITTED
AT 90°
1 m
0,6 m
37
FLUE EXAUST PIPE
Air
diaphragm
Over 20 m
No diaphr.
(hole standard)
ELBOW FITTED
AT 45°
0,5 m
0,3 m

Publicidad

Tabla de contenido
loading

Tabla de contenido