FINAL CHECKS AND TESTING
Before powering the control unit, run the following tests:
1 - Check the electrical connections: improper connection may be harmful to both the control unit and the
operator.
2 - Check proper positioning of the limit switches.
3 - Check that the red LEDs of the normally closed contacts are on and that the green LEDs of the normally open
contacts are off.
4 - Check by tripping the limit switches that the corresponding LEDs go off.
5 - Check by passing across the range of the photocells that the corresponding LED goes off.
6 - Check by tripping the safety devices that the corresponding LED goes off.
7 - Check that the motors are locked and ready for operation with the GATE AT HALFWAY TRAVEL.
8 - Remove any obstacles in the range of action of the gate and then give a START command.
Upon the first command, the control unit starts an opening phase; check that the gate moves in the correct
direction. If not, invert the wires in the OPEN - CLOSE terminals.
9 - The LEDs indicate the status of the corresponding input