Manual
Country-
Me-
Display/
spec.
nu
Setting
Settings
le-
vel
Not for IL,
P(f) Modo de servicio
1
2
3
4
4
IT
Off | Mode 1 | Mo-
de 2
Umbral de activa.
1
2
3
4
4
45 Hz – 70 Hz
Umbral de desactiv.
1
2
3
4
4
Min. 45 Hz – 61,5 Hz
Max. 45 Hz – 70 Hz
Not for IL,
Tiempo de desactiv.
1
2
4
4
3
IT
Gradiente
1
2
3
4
4
Retardo intencionado
1
2
3
4
4
Settling time
1
2
3
4
4
Rise Outg. grad. & Fall.
1
2
3
4
4
Outg. grad.
Deact. grad.
1
2
3
4
4
Fault Ride Through
1
2
3
4
Potencia reactiva
1
2
3
4
Especific. cos-phi
1
2
3
4
4
1- 0.3
Over-excited | un-
der-excited
Especific. Q
1
2
3
4
4
0 – 100%
Under-excited |
over-excited
Kaco blueplanet 29.0TL3
Configuration and operation | 9
Action in this menu/meaning
AVISO: More detailed information can be found in
F Specify the operation mode.
F Specify activation threshold (if mode 1 or mode 2 is active, this menu
option is displayed permanently for IT and IL!)
AVISO: The function is activated if the activation threshold is
exceeded. In mode 2 this value also serves as a deactivation
threshold.
. AVISO: If the grid frequency is within the deactivation ran-
ge for the duration of the deactivation time, then the
function is deactivated.
1. Specify deactivation threshold (if mode 1 or mode 2 is active,
this menu option is displayed permanently for IT and IL!).
F Specify time for power reduction (if mode 1 is active)
F Set gradient of power limitation function with increasing frequency
in % / Hz. The percentage value is based on the rated frequency (if
mode 1 or mode 2 is active, this menu option is displayed perma-
nently for IT and IL!)
F Set the power limitation delay in seconds (if mode 1 or mode 2 is ac-
tive; this menu option is displayed permanently for IT and IL!).
F Set the power reduction delay in seconds (if mode 1 or mode 2 is ac-
tive; this menu option is displayed permanently for IT and IL!).
F Specify output gradient increase and decrease in
0
/
(per thousand).
00
F Specify deactivation gradient in
0
/
(per thousand) /minute (if mode "1" or mode "2" is active. This
00
menu option is displayed permanently for IT and IL!).
AVISO: The device supports dynamic grid stabilization (Fault
Ride-Through).
F Further parameterisation is possible via the web interface
1. Open the menu: Press the Right arrow button or Enter
button.
2. Activating reactive power process: Select process a press the
Enter button. The active process is highlighted.
More detailed information about the procedure can be found at:
1. Reactive power control [Ver capítulo 10.1} Página 60]
2. Determine the specified displacement factor.
F If a power factor not equal to 1 is selected: Select the type of phase
shift: under-excited (inductive load), over-excited (capacitive load).
More detailed information about the procedure can be found at:Reacti-
ve power control [Ver capítulo 10.1} Página 60]
F Set the idle power Q (in %) to a fixed value.
F Select the type of phase shift.
AVISO: Under-excited relates to inductive load, over-excited
relates to capacitive load.
Página 47