Kaco blueplanet 29.0TL3 Serie Manual página 67

Ocultar thumbs Ver también para blueplanet 29.0TL3 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Manual
Country-
Me-
Display/
spec.
nu
Setting
Settings
le-
vel
Deactivation gradient
0 – 65534 [% / min]
Deactivation time
0 – 60000000 [ms]
Tiempo de ataque
100 – 1200000 [ms]
Núm. de pu. de ap.
Power
0,0 – 100,0 [% P
Voltage
80 – 125 [% U
Active curve
1
2
3
4
4
1 - 5
10.2.3 P(f)
Adjusting the active power P(f) in the event of overfrequency
Feed-in inverters must assist with frequency stability in the grid. If the grid frequency leaves the normal
tolerance range (e.g. ±200 mHz), then the grid will be in a critical state. In the event of overfrequency,
there is a generation surplus, in the event of underfrequency, there is a generation deficit.
PV systems must adapt their feed-in power relative to the frequency deviation. In the event of overfre-
quency, the power adjustment is determined by a maximum feed-in limit. The actual power of the in-
verter may vary freely below this limit due to a possible fluctuation in the available power or the target
value, but at no time increases above the absolute power limit.
Fig. 54: Equation 1
Fig. 55: Equation 2
Equation 1 [Ver figura 54: Equation 1 [} Página 67] defines the maximum limit with ΔP relevant to 2
[Ver figura 55: Equation 2 [} Página 67], P
ference power. In the case of PV inverters from KACO, P
time of activation. f is the current frequency and f
Fig. 56: Equation 3
Kaco blueplanet 29.0TL3
Action in this menu/meaning
If the available power is above the actual output at the time of deactiva-
tion, the power increase back to the maximum power is limited. The li-
mitation is implemented by an absolute power limitation that increases
with a continuous gradient up to the maximum power. The actual po-
wer of the inverter may vary freely below this limit due to a possible
fluctuation in the available power or the target value, but at no time in-
creases above the absolute power limit.
Only evaluated with activated hysteresis mode: Monitoring time during
which the voltage must remain below the lowest configured node befo-
re the function is deactivated.
Determines the dynamic behaviour in the event of a change in the acti-
ve power set value. With a voltage change, the active power is changed
according to a PT-1 characteristic curve with a settling time of 5 Tau.
Note: The settling time is overlaid with the increasing and decreasing
gradient.
Up to five nodes for voltage [V] and power [% Pref] are configurable.
The power value of the first and last value pair is also used as the maxi-
mum or minimum active power value that is valid across the limits of
]
the characteristic curve.
ref
]
nom
F Select active curve.
AVISO: Up to 5 characteristic curves can be configured inde-
pendently and one of them can be activated for regulation
each time.
the current power at the time of activation and P
M
Specifications | 10
is defined as P
ref
M
is the specified activation threshold.
1
the re-
ref
, the current power at the
Página 67

Publicidad

Tabla de contenido
loading

Tabla de contenido