vel
Subida secuencia neg.
constante K
Subida secuencia neg.
constante K
k 0 – 10
Bajada secuencia pos.
constante K &
Subida secuencia pos.
constante K
k 0 – 10
Banda muerta
0 - 100 [% Uref]
10.0
Solo cor. react. din.
Off | On
Modo banda inact.
Mode 1 | Mode 2
Tensión de servicio mí-
nima
45 – 125.0 [%
Unom] &
Tensión de servicio má-
xima
45 – 125.0 [%
Unom]
Contador de energía
0 – 100 % [ % Imax]
Minimum support time
1000 – 15000 ms
Kaco blueplanet 29.0TL3
Action in this menu/meaning
Amplification factor for the negative sequence used in the calculation of
the reactive current using formulae (2) and (4) Can be configured inde-
pendently for drops and spikes.
2
Amplification factor for the negative sequence used in the calculation of
the reactive current using formulae (2) and (4) Can be configured inde-
pendently for drops and spikes.
2
Dynamic grid support through fast feeding of residual current activated
in the case of voltage events with a voltage change greater than the de-
ad band.
Standard: The reactive current according to the formulae (2) and (4) is
fed as additional reactive current. The means that sum of the pre-fault
and additional reactive current is fed in.
Only dynamic: The reactive current according to the formulae (2) and
(4) is fed in as absolute reactive current. This means that regardless of
the reactive current before the voltage event, only the reactive current
is fed in according to the formulae (2) and (4) is fed in during the voltage
event.
Mode 1: When calculating the reactive current, the value of the dead
band is not subtracted from the amount of voltage change.
As such, formula (2) applies to overvoltage and undervoltage incidents.
Mode 2: When calculating the reactive current, the value of the dead
band is subtracted from the amount of voltage change. For overvoltage
and undervoltage events, formula (4) therefore applies:
I
b
1
Dynamic grid support via fast feeding of residual current is activated on
voltage events with at least one phase/phase or phase/neutral conduc-
tor voltage outside the configured normal operating voltage range. Dy-
namic grid support via fast feeding ore residual current is deactivated
when the voltage returns to the normal operating voltage range.
The reactive power component of the fast feeding of residual current is
limited to permit a defined proportion of active power components.
If due to a voltage jump in accordance with formula (1) and the configu-
red dead band is activated, the dynamic grid support is deactivated via
fast feeding of residual current after the minimum support time elapses.
Specifications | 10