INSTALLATION MANUAL
DGM1D
1-Door Mifare
controller/reader system
®
Terminal blocks:
To start your controller you must
at least put the terminals:
DIRECT LINk:
- J2: TDG1D,
- J3: Power supply and lock
(electric strikes, electromagnetic lock...).
OPTIOn:
- J5: wiring to another access control unit.
- J1: RS232 cable connected to the controller ref: PCV123D.
5] WIRING DIAGRAM: READER
Wiring of the TDG1-D: up to 2 meters.
AWG35 2 pair shielded cable.
The shield must be
connected to the GND.
Lock
Connect the lock on J3 terminal (unlock time default value
is 5 seconds).
Auto-check
When the controller is powered, the orange led on the reader
must light on during 4 seconds. After that, the led on the
reader switches off.
Earth
for the shield
Shielding
AWG35 2 pair
cable shielded
Voltage:
- Input voltage 12 Volts.
- Consumption of 300 mA max.
Request to exit input:
The push button is connected to J5 terminal.
Note: Do not put the jumper on JP4 it can prevent
the device to work properly.
Wiring of the TDG1-D: from 2 to 10 meters.
Wiring with a shielded coaxial cable
The shield must be
connected to the GND.
This product comes
with a varistor:
This one has to be mounted
directly on the terminals
of the lock (strike, EM lock...).
To secure the system from back
electromagnetic fields do not forget
to mount the varistor in parallel
on the lock.
EN
cdviberica.com
15