Uniteck UNIMPPT 60/30.24S Manual De Usuario página 27

Regulador de carga solar mppt
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

PANEL COMPATIBILITY
MAXIMUM VOLTAGE ACCEPTED BY THE REGULATOR
There are 2 panel voltages:
The operating voltage (Vmp)
Standby voltage (Voc)
To choose an MPPT, it is necessary to refer to he Voc voltage of the panel which corresponds to the
open circuit voltage.
In series the Voc add up chile in parallel not.
Example panels 100W – 12V monocrystalline (= 100W / 21.3 Voc)
In serie:
In parallel:
Uniteck recommends a parallel connection for better electrical efficiency and to avoid losses due to shading
!
+
+
= 300W and 63.9 Voc
+
+
= 300W and 21.3 Voc
UNIMPPT 60/30.24S
UNIMPPT 100/40.24S
UNIMPPT 100/50.24S
UNIMPPT 100/60.24S
*Be careful, a voltage higher than the maximum voltage (Voc) can
damage the charge regulator. Damage not covered by the warranty.
Panel voltage (Voc)
Max
60V*
100V*
www.uniteck.fr
Adated regulator
UNIMPPT 100/40.24S
UNIMPPT 60/30.24S
Min
17V (Batt 12V)
34V (Batt 24V)
17V (Batt 12V)
34V (Batt 24V)
EN
27/55

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Unimppt 100/40.24sUnimppt 100/50.24sUnimppt 100/60.24s

Tabla de contenido