MANUAL OVERRIDE

Press button(s) to toggle lights ON or OFF. Lights will remain in the last
state determined by the buttons while occupancy is detected. Sensor
will return to the programmed mode of operation when the sensor times
out. NOTE: Sensors with no buttons always operate in the Automatic
ON/Automatic OFF mode and cannot be manually turned off.
PHOTOCELL CONTROL
The photocell is used to detect if other light sources such as
sunlight, are sufficient to illuminate the space without turning on the
controlled lights. For Dual Circuit sensors, only Circuit B is
controlled by the photocell. The sensor is shipped from the factory
with the photocell control disabled. If use of the photocell is desired,
calibrate the photocell set point as follows:
1.With the light level at the desired level where the controlled lights
should be off, PRESS and RELEASE the photocell set button
using the end of a paper clip or small bladed screwdriver.
2.Step back from the sensor to avoid changing ambient light levels
in the room. During calibration the sensor will turn the lights OFF
then back ON.
3.After the calibration process, the sensor will return to its
programmed mode of operation. During occupancy, the sensor
will turn lighting OFF sixty (60) seconds after reaching or
exceeding the set point level. When the lighting level drops below
the set point level, the sensor will turn the lights ON.
ADJUSTMENTS
The following switch adjustments require that the sensor's cover
be removed. Remove the cover by inserting a small blade screwdriver
into the catch at the top of the sensor and gently pry the cover off. Set
the adjustment switches as desired (see
CONFIGURATION SWITCH SETTINGS section). Factory default
is all switches OFF. To re-install cover, place cover directly over the
sensor and align the cover's four (4) catches with the recesses in the
sensor housing. Snap cover onto housing making sure that all catches
are securely in place.
CONFIGURATION SWITCH SETTINGS – BANK A
Switch 1 – Sensor Operation Relay 1 (Default – Manual ON/Auto-
matic OFF)
Note: This switch is disabled for 2001 series vacancy sensors.
Programs the sensor for either Manual ON/Automatic OFF
operation or Automatic ON/Automatic OFF operation. When set to
Manual ON/Automatic OFF mode, lights are turned ON by
manually pressing the ON/OFF button. If the sensor times out and
turns the lights OFF in the Manual ON/Automatic OFF mode while the
space is still occupied, any motion detected within thirty (30) seconds
will automatically turn the lights back ON, without requiring the user to
press the ON button.
Switch 2 – Dual Circuit Relay 2 (Default – Manual ON/
Automatic OFF)
Note: This switch is disabled for 2001 series vacancy sensors.
Programs the sensor for either Manual ON/Automatic OFF
operation or Automatic ON/Automatic OFF operation. When set to
Manual ON/Automatic OFF mode, lights are turned ON by
manually pressing the ON/OFF button. If the sensor times out and
turns the lights OFF in the Manual ON/Automatic OFF mode while the
space is still occupied, any motion detected within thirty (30) seconds
will automatically turn the lights back ON, without requiring the user to
press the ON button.
Switch Bank A
1
Sensor Operation Relay 1
2
Dual Circuit Relay 2
3
4
5
Switch Bank B
1
2
Time
3
Passive Infrared
4
5
PD2611
Page 2
Function
Timer Mode
Adaptive Reset
Relay Bypass
Function
Timer Select 0
Timer Select 1
Ultrasonic
Sensitivity
04/15
Switch 3 – Adaptive or Fixed Timer (Default – Adaptive)
Controls selection between Adaptive Timer Mode and Fixed Timer
Mode. In Adaptive Timer Mode, the sensor automatically self-adjusts
its timeout delay to optimize energy savings. The sensor will initialize
its timer value to eight (8) minutes. If the Bank B Timer Select 0 and
Timer Select 1 switches have been set to four (4) minutes, this will be
the smallest timer value used. In Fixed Timer Mode, the sensor's self-
adapting timer functions are disabled and the sensor's timeout delay is
set according to the Bank B Timer Select 0 and Timer Select 1 switch
settings.
Switch 4 – Adaptive Reset (Default – Off)
The sensor is equipped with Hubbell patented self-adaptive Intelli-
DAPT® technology which automatically adjusts the sensor's sensitiv-
ity and timer settings to optimize performance based on occupancy
patterns. The sensor constantly learns and adjusts appropriately. If the
learned settings need to be reset (e.g. when relocating sensor to an-
other area), toggle the switch ON then OFF. The adaptive timer is reset
according to the Bank B Timer Select 0 and Timer Select 1 switches.
The adaptive sensitivity (both PIR and Ultrasonic as applicable) are
reset to
factory default. The photocell sensor settings are also reset to
factory default (disabled) such that the sensor will turn on the light(s) in
response to occupancy regardless of ambient light levels in the lighted
space. NOTE: Adaptive reset can also be achieved by pressing and
holding the photocell set button for ten (10) seconds.
Switch 5 – Relay Bypass (Default – Off)
If it is necessary to service the controlled circuits without de-energizing
them at the breaker panel (NOTE: this is not recommended as a stan-
dard procedure), perform the following steps:
1.With the lights ON, set the relay bypass switch to the ON
position.
2.Push the button(s) to turn the lights OFF.
3.Push the button(s) again to verify override (lights should not
come back on).
The relay bypass switch will now interrupt sensor operation,
preventing output(s) from turning ON again, regardless of
occupancy or pushbutton conditions. To return the sensor to
normal operation, flip the relay bypass switch to the OFF position.
To confirm sensor is operating normally, lights should now turn
ON and OFF when the button(s) are pressed.
CONFIGURATION SWITCH SETTINGS – BANK B
Switches 1 and 2 – Timer Settings (Default – 8 min)
Sets the length of time lights will remain ON after last motion is de-
tected. The timeout value can be set to 4, 8, 16 or 30 minutes. See
Bank A – Switch 3 - Adaptive or Fixed Timer section for additional
information.
Switches 3 and 4 – Sensing Technology Enable/Disable
fault – Enable)
Enables or disables the occupancy sensing technologies used by the
sensor.
Switch 5 – Sensitivity (Default – High)
Sets the sensor's initial Passive Infrared (PIR) and/or Ultrasonic sensi-
tivity level. Sensitivity can be set to either High or Low.
OFF (Default)
Manual ON / Automatic OFF
Manual ON / Automatic OFF
Adaptive
Enable Adaptation
Normal Operation
OFF
Æ
Å
4 min
Enabled
Enabled
High
ON
Automatic ON / Automatic OFF
Automatic ON / Automatic OFF
Fixed
Restore Factory Defaults
Relay Override
ON
Å
Å
Å
Æ
8 min
16 min
Disabled
Disabled
Low
(De-
Æ
Æ
30 min