Pressure Testing

The appliance must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 PSIG (3.5 kPa).
This appliance, as well as its individual shut-off valve, must
be disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in excess
of 1/2 PSIG (3.5 kPa).
When checking appliance regulator function, make certain
pressure of natural gas supply is between 6 and 14 inches
of water column or, if converted for LP gas, between 11 and
14 inches.
THE PRESSURE TESTING SHOULD BE PERFORMED BY
MEANS OF THE INJECTOR THREAD ZONE
Gas test inlet
Thread Pressure

Pressure Test Method

• Remove grate and burner cap
• Remove aluminum gas spreader
• Temporarily remove the injectors
• Connect the pressure Test instrument into injector holder
thread zone (M6x0,75)
• Check if the cooktop has the correct pressure
• Fix the injector removed for testing and replace the parts
in the right position.