Installation of outdoor unit
Step 1: Fix the support of outdoor
Select it according to the actual installation situation
1. Select installation location according to the house structure.
2. Fix the support of outdoor unit on the selected location with expansion screws.
Note:
● Take sufficient protecttive measures when installing the
outdoor unit.
● Make sure the support can withstand at least four times
of the unit weight.
● The outdoor unit should be installed at least 3cm above
the the floor in order to install drainjoint.
● For the unit with cooling capacity of 2300W~5000W, 6
expansion screws are needed; for the unit with cooling
capacity of 6000W~8000W, 8 expansion screws are
needed; for the unit with cooling capacity of 10000W
~16000W, 10 expansion screws are needed.
Step 2: Install drain joint and chasis rubber plug
chasis rubber plug
Step 3: Fix outdoor unit
1. Place the outdoor unit on the support.
2. Fix the foot holes of outdoor unit with bolts.
1. Connect the outdoor drain joint into the hole on
2. Connect the drain hose into the drain vent.
3. For chasis eletric heater equiped unit, there are
Note:
drain joint
There is no drain joint and chasis rubber plug for
some unit, please refer to accessary package.
the chassis, as shown in the picture below.
several drain holes on the chasis, which is used
for quick drainage to avoid chasis freeze in cold
area. If there is no need for quick drainage, please
fix the rubber plug into chasis. According to drain
hole shape, select corresponding plug to fix into
holes from the bottom, shown as the left.
42
at least 3cm above
the the floor