Dip-Switch Setting; Setpoint Dynamics - AERMEC UFB W Serie Manual De Instrucciones E Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

35.

DIP-SWITCH SETTING

The board has specific configuration dip-switches
for the possible installations. There are 8
microswitches are and they have the following
functions:
DIP
DIP 1
DIP 2
DIP 3
DIP 4
DIP 5
DIP 6
DIP 7
DIP 8
36.

SETPOINT DYNAMICS

With the VMF-E4 user interface it is possible
to select the regulation temperature value,
the excursion range of this value depends on
the operation mode or the dead band (see the
following tables).
Min Set
12°C
12°C
17°C
Min Set
12°C
12°C
14°C
27
IUFBTY 1601 - 5495900_01
THERMOSTAT DIP-SWITCH CONFIGURATION
POSITION
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Setting the temperature with dead band of 5°C
Central set
12°C
20°C
25°C
Setting the temperature with dead band of 2°C
Central set
12°C
20°C
22°C
FUNCTION
With shut-off valve
No shut-off valve
Water probe upstream of the valve
Water probe downstream of the valve
Continuous ventilation
Thermostat-controlled ventilation
Reduced band enabling
Normal band enabling
4-tube air treatment unit
2-tube air treatment unit
Renewal air bypass present
Renewal air bypass not present
Dead band 2°C
Dead band 5°C
Minimum continuous speed 10%
Minimum continuous speed 20%
Max set
12°C
28°C
33°C
Max set
12°C
28°C
30°C
Operating mode
Anti-freeze
Heating
Cooling
Operating mode
Anti-freeze
Heating
Cooling

Publicidad

Tabla de contenido
loading

Tabla de contenido