3.3.2 FIN-180B-HW
Risk of electric shock. Electrical wiring must be done by qualified personnel in
accordance with all applicable codes and standards. Before connecting wires, switch
power off at service panel and lock service disconnecting means to prevent power from
NOTE: The insulated duct not shown to simplify the illustration below.
1.
Detach the electrical compartment cover from the unit by removing its retaining screw.
2.
Install the included wire clamp on the unit. Insert the house wiring cable through the wire clamp and
tighten the wire clamp to secure the cable.
3.
Using provided wire connectors, connect wires as follows: BLACK to BLACK, WHITE to WHITE
and GREEN or BARE wire under ground screw. DO NOT FORGET TO CONNECT THE GROUND.
4.
Put back in place the electrical compartment cover, taking care not to pinch wires. Restore power at
service panel.
Ground screw
VE0424
3.4 T
EST THE UNIT
You may test the unit at this point using the test port on the intake side (closest to the filter) and a Pitot tube.
The distance between the test port and the center of the duct is 3.75 inches.
If the unit is connected to an AHU, make sure that the AHU is not
running while measuring the airflow.
⚠
WARNING
being switched on accidentally.
9 9
Test ports
VD0472