FDI 94 FDI 124 FDI 184 FDI 244 MANUAL DE INSTALACIÓN
11. If the unit has an auxiliary electric heater, it must be installed at least 1 meter (40in) away from any
combustible materials.
WARNING BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO
THE SYSTEM.
1. Prepare the cable for connection:
Use the right cable
• Indoor Power Cable (if applicable): H05VV-F or
H05V2V2-F
• Outdoor Power Cable: H07RN-F
• Signal Cable: H07RN-F
a. Using wire strippers, strip the rubber jacket from both ends of cable to reveal about 15cm (6in) of the
wires inside.
b. Strip the insulation from the ends of the wires.
c. Using a wire crimper, crimp u-lugs on the ends of the wires.
PAY ATTENTION TO LIVE WIRE While crimping wires, make sure you clearly distinguish the Live ("L") Wire
from other wires.
WARNING ALL WIRING MUST PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIRGRAM
LOCATED INSIDE THE OUTDOOR UNIT S WIRE COVER.
2. Unscrew the electrical wiring cover and remove it.
3. Unscrew the cable clamp below the terminal block and place it to the side.
4. Match the wire colors/labels with the labels on the terminal block, and firmly screw the u-lug of each wire
to its corresponding terminal.
5. After checking to make sure every connection is secure, loop the wires around to prevent rain water from
flowing into the terminal.
6. Using the cable clamp, fasten the cable to the unit. Screw the cable clamp down tightly.
7. Insulate unused wires with PVC electrical tape. Arrange them so that they do not touch any electrical or
metal parts.
8. Replace the wire cover on the side of the unit, and screw it in place.

REFRIGERANT PIPING CONNECTION

60