preparing the boiler for operation
Module programming
The are two options:
Scenario no. 1: the boiler includes a BUS BridgeNet® connection;
confi gurations are made from the boiler or from an the system inter-
face (option).
Scenario no. 2: the module is independent, and the zones are confi -
gured from the system interface supplied as an option.
Initialisation
Before starting the procedure, check that all the circuits have water
and that the purge was carried out correctly.
Once all equipment is connected, the system recognises the equip-
ment and carries out automatic initialisation.
key
Confi guring the module
1) Switch on the display by pressing the OK key. The screen is activa-
ted.
2) Press and hold the
simultaneously for 5 seconds.
3) Using the "encoder" button, display code 234 then confi rm with
the OK key.
4) Turn the button clockwise to access the MENU option then con-
fi rm with the OK key.
5) Look for menu 7 "Multizone Module" using the "enco-
der" button then confi rm with the OK key. Select sub-menu
72 "Multizone" then confi rm with the OK key. Select parameter
720 then confi rm with the OK key and select MGm II parame-
ter 2 or MGm II parameter 3 then confi rm with the OK key.
Confi guring the module from the boiler
1) Press the menu/ok key. When CODE is displayed, press menu/ok;
code 222 will appear.
2) Turn the "encoder" button to the right then display code 234 and
confi rm with the menu/ok key.
3) MENU appears on the screen; confi rm then select menu 7 and
confi rm with the menu/ok key.
4) Select sub-menu 72 and confi rm with the menu/ok key.
5) Select sub-menu 720 and confi rm with the menu/ok key.
6) Select parameter 2 for MGm II and parameter 3 for MGm III and
confi rm with the menu ok key (see Menu 720 in the settings
table).
7) Press the esc key repeatedly to return to the boiler display.
48
OK key
OK
Encoder
using the system interface
and OK keys on the system interface

Air bleeding

The module's automatic air bleed function is only activated from the
boiler if there is a BUS BridgeNet® connection (scenario no. 1).
The air bleed function is activated by pressing and holding the esc
key on the boiler for 5 seconds or by activating parameter 7 0 1.
With the bleed function activated, the module performs an ON/OFF
circulating pump, the mixing valve. This causes the air in the circuit to
start circulating. You can activate a new cycle if necessary.

Frost protection function

If the fl ow sensor records a temperature lower than 5°C, the frost
protection function is activated. If the frost protection function is
activated, the module starts the circulating pump. This allows frost
protection to be extended to zones 1 and 2.
Anti-jamming function
After every 24 hours of inactivity, an anti-jamming cycle is performed
on the circulating pump and the mixing valve.