3: U
C
SER
ONFIGURABLE
O
PTIONAL
F
UNCTION
Automatic Self-Test
UPS ID
Date of Last Battery
Replacement
Minimum Capacity
Before Return from
Shutdown
Alarm Control
Shutdown Delay
Synchronized Turn-on
Delay
Output Voltage
Voltage Sensitivity
The uninterruptible
power supply detects
and reacts to line voltage
distortions by transfer-
ring to battery operation
to protect connected
equipment.
Low Battery Warning
I
TEMS
N
: S
OTE
ETTINGS ARE MADE THROUGH THE SUPPLIED
S
S
MART
LOT ACCESSORY CARDS
F
ACTORY
D
EFAULT
Every 14 days
(336 hours)
UPS_IDEN
Manufacture Date
0 percent
Enable
90 seconds
0 seconds
750THV, 1000THV
and 1500THV mod-
els:
230VAC
High
2 minutes
PowerChute software
provides automatic,
unattended shutdown
when approximately
two minutes of bat-
tery operated runtime
remains.
9
P
C
OWER
HUTE SOFTWARE OR
. R
EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS
U
S
SER
ELECTABLE
C
HOICES
Every 14 days
This function sets the interval at which the
(336 hours),
uninterruptible power supply will execute a
Every 7 days
self-test.
(168 hours),
On Startup Only,
No Self-Test
Up to eight characters
Use this field to uniquely identify the unin-
terruptible power supply, (i.e. server name
or location) for network management pur-
poses.
mm/dd/yy
Reset this date when you replace the battery
module.
0, 15, 30, 45, 50, 60, 75,
The uninterruptible power supply will
90 percent
charge its batteries to the specified percent-
age before it powers up connected equip-
ment, following a low-battery shutdown.
Enable, Mute, Disable
User can mute an ongoing alarm or disable
all existing alarms permanently.
0, 90, 180, 270, 360,
The interval is set between the times when
450, 540, 630 seconds
the uninterruptible power supply receives a
shutdown command and actual shutdown.
0, 60, 120, 180, 240,
The uninterruptible power supply will wait
300, 360, 420 seconds
the specified time after the return of utility
power before turn-on (to avoid branch cir-
cuit overload).
750THV, 1000THV and
750THV, 1000THV and 1500THV models:
1500THV models:
Allows the user to select the output voltage.
220, 230, 240VAC
Adjust by pressing the voltage sensitivity
: Brightly illumi-
button
nated - high sensitivity.
ject (such as a pen) to do so.
: Dimly illuminated
Note: In situations of poor power quality,
- medium sensitivity.
the uninterruptible power supply may fre-
quently transfer to battery operation. If the
: No illumination;
connected equipment can operate normally
low sensitivity.
under such conditions, reduce the sensitivity
setting to conserve battery capacity and
service life.
The uninterruptible power supply will beep
when two minutes of battery runtime re-
: Brightly illumi-
mains.
nated - low battery
warning level of about
Change the warning interval setting by
two minutes.
pressing the voltage sensitivity button, while
: Dimly illuminated
pressing and holding the
- low battery warning
Change the low battery warning interval
level of about five min-
setting to the time that the operating system
utes.
or system software requires to safely shut
down.
: No illumination;
low battery warning
level is approximately
eight minutes.
Possible interval set-
tings: 2, 5, 8, 11, 14, 17,
20, 23 minutes.
.
D
ESCRIPTION
(rear panel). Use a pointed ob-
button.