powered through the dual door interface module. Refer to the reader
manufacturer specifications for cabling requirements.
Reader wiring
1
2
3
4
5
6
7
Callout
Description
1
Buzzer
2
+14 V
3
Green LED
4
Red LED
Wiring In and Out readers
CN10/CN17
1
2
3
BZ 14 GR RD D1 D0 0
2
1
3
23
22
21
20
19
18
17
TruPortal System Controller Quick Reference
CN10/CN17
CN11/CN18
Callout
Description
5
Data1
6
Data0
7
Ground
CN11/CN18 CN12/CN19
1
2
3
4
1
2
A B
4
6
8
5
7
9
11
12
13
14
15
16
Callout
Description
1
Buzzer
2
+14 V
3
Green LED
4
Red LED
5
D1
6
D0
7
0 V
8
D1
9
D0
10
Reader (Out)
11
Ground
12
Power
Input Circuit Wiring
Typically, these inputs are used to monitor door position, request to exit, or
alarm contacts. Input circuits are supervised. The input circuit is able to
report a condition of "Fault" for the status of the circuit, which appears as a
"Tamper" event for supervised conditions.
A supervised input circuit requires a resistor be added to the circuit to
facilitate proper reporting. The standard supervised circuit requires 1K ohm,
1% resistors and should be located as close to the sensor as possible.
Relay Circuit Wiring
All relays are dry contact.
Output
Siren relay
10
Strobe relay
Strike relay
Aux relay
The relays for siren and door strike have a Common pole (C), a Normally
Closed pole (NC), and a Normally Open pole (NO). When you are
controlling the delivery of power to the door strike, the Normally Open and
Common poles are used. When you are momentarily removing power to
unlock the door, as with a mag lock, the Normally Closed and Common
poles are used. Check with local building codes for proper egress door
installation.
Power
The TruPortal System Controller requires 18 VAC or 24 VDC for input
power at CN2, or 12 VDC at CN1 (24 VDC and 12 VDC input power were
not evaluated by UL). When powering the board from 12 VDC, the on-
board battery charger will not be used and the lead-acid backup battery
3
Callout
Description
13
LED
14
Buzzer
15
Data0
16
Data1
17
Data1
18
Data0
19
Buzzer
20
LED
21
Power
22
Ground
23
Reader (In)
30 VDC rating
1 A
1 A
5 A
1 A
P/N 460800001B 12JAN12 en-US