Power Setup; Configuration - Interlogix TP-SYS-BRD Referencia Rápida

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Mains Supply
Item
North
America
product
Internal
120 VAC +10%
transformer
-15%, 60Hz
Input current
600 mA
rating (AC)
Mains fuse
T630 mA
250 V, UL
Listed
Warning: For continued protection against risk of fire, replace the mains
fuse only with the same type and rating of fuse.
The Aux. DC supply output is a Class 2 Power Limited circuit.
Aux DC Supply
Item
Mains
powered
unit
Output voltage
14 V ±5%
(DC)
Standby
7 Ah or 18 Ah
battery
Maximum
24 hours
recharge time
DC power
2.4 A
supply
rating**
Battery charge
1.2 A
limit
Quiescent
140 mA
current
* 24 VDC and 12 VDC input were not evaluated by UL.
** This DC Power Supply Rating is for all the current requirements,
including recharging the battery.
Board protection is provided by resettable fuses which are not replaceable.
All wiring in this enclosure is required to be UL compliant. All installation
wiring within this equipment cabinet should utilize plastic cable ties to
bundle cables and attach to designated cabinet cable mounting locations to
provide strain relief for the cable harness.
Disposal of batteries should be according to the local laws and regulations
of your region. Contact your local waste management office for information
on battery recycling or disposal.
If you are not able to identify the applicable rules in your area, check the
instructions which will be available from the battery manufacturer.
Ground all enclosures in accordance with NFPA 70 and Canadian Electrical
Code, Part I.
TruPortal System Controller Quick Reference
European
Australian/
product
New Zealand
product
230 VAC +10%
240 VAC
-15%, 50Hz
±10%, 50Hz
250 mA
250 mA
T400 mA
T400 mA
250 V
250 V
+24 VDC
+12 VDC
input*
input*
14 V ±5%
12 V ±5%
7 Ah or 18 Ah
24 hours
2.4 A
1.2 A
1.2 A
140 mA
200 mA

Power Setup

Power management parameters for the TruPortal System Controller are pre-
configured as follows. These parameters can not be changed:
Brownout mode: Alarm and report
Brownout voltage (V): 10.00
Battery size (Ah): 18
Select Check for battery.
Clear the Enable battery tests check box.
Test time: 10 sec
Low load test period: 3 min
High load test period: 20 hr
Low voltage (V): 11.70
Warning voltage (V): 11.40
Cutoff voltage (V): 10.20
Very low voltage (V): 9.00
Excess charge voltage (V): 16.00
Cutoff time: 10 sec
No current (mA): 17
Excess power state discharge current (A): 1.200

Configuration

Use the TruPortal Installation Wizard to discover the controller and
connected peripherals, and to change basic configuration parameters.
1.
Insert the TruPortal disc in your computer's CD/DVD drive (Windows
only).
2.
Install Microsoft .NET 4.0 Framework.
The TruPortal Utilities software will detect automatically if the .NET
software is installed and display the word "Installed" next to the link if
it is found.
3.
Install Bonjour Print Services.
The TruPortal Utilities software will detect automatically if the
Bonjour software is installed and display the word "Installed" next to
the link if it is found.
4.
Click Discovery and Installation Wizard.
5.
Select a Language and click [Next].
The wizard will search the network for all TP controllers.
6.
Select the controller to configure from the list and click [Next].
7.
Type the Administrator's current Password.
The default administrator User Name is
The default administrator Password is
8.
Choose a new password for the administrator.
The Administrator account has access to all aspects of the TP
controller configuration. Leaving default user names and passwords in
place is dangerous. Anyone familiar with the product will know the
defaults.
9.
Type the password in the New Password and Confirm Password
fields and click [Next].
10. Change the settings on the Network Configuration tab as directed by
the site's network administrator.
5
admin
demo
P/N 460800001B 12JAN12 en-US