TruPortal Reader Output LEDs
The following chart describes the behavior of TruPortal reader output based
on different actions of the door.
Reader Mode
1
Disabled
2
Unlocked
3
Locked
4
Facility
N/A
5
Card Only
6
Pin Only
7
Card & Pin
8
Card or Pin
Replace Battery
The event log buffer and the real time clock are backed up by a 3 V battery.
Without power being applied to the controller, the battery will retain events
and transactions for up to one year.
This battery should be replaced annually to insure that proper backup
functionally is maintained. Remove the insulator from the battery holder
after installation. Replacement battery: Panasonic CR2354 Lithium coin cell
battery.
Warning
Caution:
Specifications
The TruPortal System Controller is for use with UL Listed access control
power limited power supplies. These specifications are subject to change
without notice.
•
Primary Power:
-
AC power: 18 VAC ± 10%
-
DC power: 24/12 VDC ± 10% (Not evaluated by UL.)
-
Maximum input power: 2.7 A
-
Total current that can be sourced from panel: 1 A.
Note:
It is up to the installer to ensure that the sum of the loads on all
the supply outputs from the TruPortal System Controller plus the
current consumed by the controller is equal to or less than 1.2 A
(see power table). The 1.2 A output current from the regulator
also includes at least 200 mA to power the I/O board and the
TruPortal System Controller Quick Reference
GREEN
GREEN
RED
GREEN
RED
RED
N/A
RED
RED
RED
RED
RED
RED
RED
RED
When changing the lithium battery,
replacement must be a Panasonic
CR2354 only.
Battery may explode if mistreated. Do not
recharge, disassemble or dispose of in
fire. Follow local code for proper disposal
of used lithium battery.
LED
N/A
30
0
0
0
5
0
0
0
30
0
0
0
30
0
0
0
30
0
0
0
30
0
0
0
30
0
0
0
SOM. Maximum available output current is 1 A. [Example:
250 mA for (Reader power) + 400 mA for (SNAPP Ports) =
650 mA total current used.] Drawing more will cause the output
voltage to drop as the system regulator starts to current limit.
-
The power applied from the mains to the transformer in the
enclosure is 120 VAC for North America (230 VAC for Europe,
and 240 VAC for Australia).
•
Memory and Clock Backup: Panasonic 3 V CR2354 Lithium coin cell
battery
•
Wiring
-
Ground: 14 AWG (1.628 mm / 2.08 mm
from the fused terminal block to the ground lug
-
Module Bus (RS-485) Cabling (device communication and
power): Recommended: 22 AWG (0.644 mm / 0.326 mm
4 conductors, shielded twisted pair, 120 impedance, low
capacitance, 41 pF/meter or 12.5 pF/foot (such as Belden 9842).
-
Maximum Length: Up to 2000 feet (610 m) of cable on a Module
bus port.
Note:
For longer cable distances, or where one cable connects many
expansion modules (daisy chained, star wiring configurations are
not acceptable), a 120-ohm terminating resistor will need to be
installed across A and B communication terminals of the last
module on the bus cable.
-
Separate Power (or door strike) Wiring: Recommended:18 AWG
(1.024 mm / 0.823 mm
color-coded is preferable)
-
Inputs/Sensor Cabling: 22 AWG (0.644 mm / 0.326 mm
2 wires (For electrically noisy environments, use twisted pair,
and/or shielded cable.)
-
Outputs/Signaling: 22 AWG (0.644 mm / 0.326 mm
2 conductors
•
Reader Cabling: 22 AWG (0.644 mm / 0.326 mm
Listed installations: 22 AWG / 0.644 mm / 0.326 mm
Maximum for reader data lines: 500 feet (150 m). Maximum for power
wiring: 300 feet (91.44 m).
7
N/A
N/A
2
),, provided in the panel
2
), stranded and insulated (2 conductors;
2
),(For Canadian UL
P/N 460800001B 12JAN12 en-US
2
),
2
),
2
),
2
), shielded.