4.5 System configuration
The configuration of the base station is done optionally via the microSD, the software interface of
the Ethernet variant or the Service level of the room control unit Bus Display.

4.5.1 System configuration with microSD card

Individual settings can be made via the EZR Manager SD Card under www.ezr-home.de and
transferred to the base station via the microSD card. As of software version 01.70, the base station
accepts microSD cards >2 GB in the formats FAT16 or FAT32.
¾ Open www.ezr-home.de in the web browser of your PC, select EZR Manager SD Card and
follow the instructions on-line.
¾ Insert the microSD card with the updated data into the base station.
9 The transfer process will start automatically and copy the updated data into the base sta-
tion.
9 The LED "syBUS" flashes during the transfer process.
9 After a successful data transmission, the LED "syBUS" goes out.
DEU

4.5.2 Configuration with room control unit Wireless Display

ENG
The Service level of the base station Wireless Display is protected with a PIN code and may only
be used by authorized specialists.
FRA
Attention! Faulty configuration leads to errors and damage to installations.
¾ Press the rotary control.
NDL
¾ Select the menu "Service Level" and activate by pressing.
¾ Enter the 4-digit PIN (standard: 1234) by rotating and pressing.
ITA
¾ Select parameters (PAr) by pressing again and enter the number code of the desired param-

ESP

eter (see following table).
¾ Change parameters as required and confirm by pressing.
No.
Parameters
010
Used heating system
020
Heating/cooling block
030
Operation lock
(child safety lock)
031
Operating lock password
34
Description
Adjustable per heating zone: Floor heating (FBH) standard /
FBH low energy / radiator / convector passive / convector
active
Blocking the switching outputs depending on the activated
operating mode (heating/cooling)
Unlocking the operating lock with password protection
Determine PIN if parameter 30 is set to active
Unit
FBH St.=0
FBH NE=1
RAD=2
KON pas.=3
KON act.=4
normal=0
Heating block=1
Cooling block=2
Deactivated=0
Activated=1
0000..9999