Contactores, contactos auxiliares

Publicidad

General
100(S)-E and 300(S)-GO, -HO contactors are i f tted with an electronic coil interface. For a given coil this interface allows the contactor to accept a very
wide voltage range. The contactor can also be controlled by separate logic control signals from, for instance, a PLC. Selection of control method is
done with switch S1. Control by switching voltage on A1 and A2 requires the switch in position B while control logic signals requires the switch
in position A. Use of the logic control signals also requires a steady supply voltage on A1 and A2 within the rated voltage range.
Control by switching voltage on A1 and A2 (switch S1 in position B default factory setting)
Operation of 100(S)-E and 300(S)-GO, -HO cont actors can be done as with conventional contactors by applying and removing voltage on A1 and A2.
Control with logic control signals (switch S1 in position A)
Use of the logic control signals also requires a steady voltage on terminals A1 and A2 within the operational limits. Minimum pulse length for opening and closing: 7ms.
The function of the logic control signals will no longer be guaranteed when the voltage on A1 and A2 is removed. The logic control signals operates with 24V DC and
consists of two control signals (ON and OFF_N) and a common reference (COM). The contactor is closed by a control signal ON and opened by removal of control signal
from OFF_N
Supply voltage
+24 V
Start
Contactor
X5
ON
1
Stop
OFF_N
2
COM
3
95
96
OV
Note: Emergency stop should disconnect A1 and A2
When used with switches the wiring can be done
according to diagram above.
ON
OFF_N COM
X5
1
2
3
The functions are descibed with following diagram. "1" means 24V DC
between the control signal and COM, "0" means no voltage between the
control signal and COM. The function is made so that ON and OFF_N can
be connected in parallel for a common ON/OFF signal. In addition to these
signals the function limits for the supply voltage are still valid (closing at
85% and opening at 55%), which is indicated in the diagram by high and
low voltage.
Notice!
This product has been designed for environment A. Use of this product in environment B may cause unwanted electromagnetic disturbances
in which case, the user may be required to take adequate mitigation measures.
Aviso!
Este produto foi projetado para o ambiente A. O uso deste produto em ambiente B pode causar perturbações eletromagnéticas indesejadas,
cujo caso o usuário poderá ser obrigado a tomar medidas de mitigação adequadas.
Attention!
Ce produit est conçu pour un environnement A. L'utilisation de ce produit dans un environnement B peut provoquer des perturbations
électromagnétiques indésirables, auquel cas l'utilisateur devra peut-être prendre des mesures d'atténuation appropriées.
Avviso!
Questo prodotto è stato concepito per essere utilizzato in ambiente A. L'utilizzo di questo prodotto in ambiente B può comportare la generazione
di interferenze elettromagnetiche indesiderate per cui l'utente dovrebbe adottare le necessarie contromisure.
Hinweis!
Dieses Produkt ist für Umgebung A ausgelegt. Die Verwendung dieses Produkts in Umgebung B kann zu unerwünschten elektromagnetischen
Störungen führen. In diesem Fall muss der Benutzer entsprechende Gegenmaßnahmen ergreifen.
¡Aviso!
Este producto ha sido diseñado para el ambiente A. El uso de este producto en el ambiente B puede provocar perturbaciones electromagnéticas
no deseadas. En tal caso el usuario puede tener que tomar medidas de mitigación apropiadas.
!
注意!
本产品设计用于环境 A。在环境 B 中使用本产品可能会导致有害的电磁干扰,用户在这种情况下需要采取充分的缓解措施。
通知!
本製品は環境A向けに設計されました。環境Bで本製品を使用すると、望ましくない電磁波による障害を引き起こす可能性があります。
その場合、ユーザは十分な緩和措置をとる必要があります。
이 제품은 환경 A에 맞게 설계되었습니다. 이 제품을 환경 B에서 사용하면 전자파 장해가 발생해 사용자가 적절한 완화 조치를 취해야 할 수 있습니다.
참고!
+24 V
A1
A2
Start
Stop
0V
Relay
Note: Emergency stop should disconnect A1 and A2
When used with transistor outputs the wiring can be done
according to diagram above.
X 5
1
2
3
S 1
A
B
PLC
PLC
S1
A
B
.
Supply voltage
A1
A2
Contactor
X5
ON
1
OFF_N
2
COM
3
Relay
95
96
Wire dimensions for PLC interface.
3 x 0.2...2 mm²
3 x AWG 22 ... 14
O N
O F
F _
C O
N
M
P L
C
P L
C
ON
OFF_N
Supply voltage
on A1 and A2
Closed
Position
A.
Position
Contactor
closed
Contactor
open
Low
Normal range
Operationalrange
85% of lower voltage range level
55% of lower voltage range level
Wire strip length
5-6 mm
(0.2-0.24 in)
X 5
O N
1
O N
2.6 lb-in
2
O F
0.3 Nm
F _
3
N
C O
M
S 1
A
P L
B
C
P L
C
ø 3.5 mm
(0.14 in)
24V DC Signals:
Status "1" : U =15...33V DC
I =10mA at 24V
Status "1" : U =0...5V DC
1
0
1
0
1
0
Open
B
4/5
Contro l