According to UL 60947-4-1
Use wire Cu 75
°C
only.
100(S)-E400, E460, 300(S)-GO : Enclosure with min 36 by 30 by 12 inches should be used.
100(S)-E580, E750, 300(S)-HO : Enclosure with min 48 by 36 by 16 inches should be used and secured by at least three latches.
100-E1260: Enclosure with min 78.75 by 39.4 by 23.6 inches should be used.
UL Short Circuit data
Suitable for use on a circuit capable of delivering not more than the max symmetrical amperes at the max voltage shown on the table below.
Type 1
100(S)-E400
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
100(S)-E460, 300(S)-GO
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
100(S)-E580, 100(S)-E750, 300(S)-HO
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
Type 2
100(S)-E400
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
100(S)-E460, 300(S)-GO
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
100(S)-E580, 100(S)-E750, 300(S)-HO
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
Additional Ratings
100(S)-E400
Capacitor Switching
208 V, 119 kvar, 330 FLA
240 V, 137 kvar, 330 FLA
480 V, 274 kvar, 330 FLA
600 V, 343 kvar, 330 FLA
After a short circuit, ensure that the quarter turn cover screws are in the correct position
For applications above 690V, terminal shrouds 100-ETS460L or 100-ETS750L should be used.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 100-IN053C-EN-E December, 2018
140G-M0
140G-M
1000/L
800/L
18
84
18
100
42
140G-M
140G-M0
1000/L
800/L
18
84
30
100
42
140G-M0
140G-M0/N0
1200/L
1200/L
30
89
30
100
42
140G-M
140G-M6
600/J
600/J
18
65
18
100
35
140G-M
140G-M6
600/J
600/J
18
65
30
100
35
140G-M0
140G-M6
1200/L
1200/L
30
65
30
100
35
100(S)-E460, 300(S)-GO
100(S)-E580
208 V, 142 kvar, 396 FLA
208 V, 178 kvar, 495 FLA
240 V, 164 kvar, 396 FLA
240 V, 205 kvar, 495 FLA
480 V, 329 kvar, 396 FLA
480 V, 411 kvar, 495 FLA
600 V, 410 kvar, 396 FLA
600 V, 514 kvar, 495 FLA
100-E1260
140G-N6
140G-N0
42
42
42
42
100(S)-E750, 300(S)-HO
208 V, 214 kvar, 595 FLA
240 V, 247 kvar, 595 FLA
480 V, 494 kvar, 595 FLA
600 V, 618 kvar, 595 FLA
1600/L
100