All local and national laws and European standards must be
met when installing and using the appliance. In Italy, refer to
the UNI 10683/2012 standard, as well as any regional or local
health authority regulations
It is necessary to refer to regulations in force in each country. If
installing in an apartment building, check with the management
DEVICES
The stove MUST NOT be installed in the same space as type B
gas heating equipment (e.g. gas boilers, stoves, and equipment
units work.
The stove is supplied with a power cable that is to be connected
mic switch. Voltage variations exceeding 10% can damage
the stove (unless already installed, an appropriate differential
system. The power line must have a suitable cross-section for
the stove's power. An inadequate earthing system can cause
anomalies for which Edilkamin cannot be held liable.
POSITIONING
The stove must be level for it to function correctly.
FIRE PREVENTION SAFETY DISTANCES
The stove must be installed in compliance with the following
safety conditions:
and back of the stove: 20 cm
the front of the stove.
If it is not possible to comply with the above mentioned
distances, technical and construction-related provisions
must be appropriately insulated
AIR INTAKE
The room where the stove is located must have an air intake
with cross section of at least 80cm2 to ensurereplenishment
of the air consumed by combustion.Alternatively, the stove
air may be taken directly from outside through a 4 cm steel
extension of the pipe.
In this case,there may be condensation problems and it is ne-
cessary to protect the air intake with a grille, which must have
a freesection of at least 12 cm².
The pipe must be less than 1 metre long and have no bends.
with a wind guard. In any case all the way air intake duct must
be a free section of at least 12 cm².
The external terminal of the air inlet channel must be protected
with an anti-insect netting that does not reduce the
12 cm² through passage.
INSTALLATION
MOKE OUTLET
The smoke is discharged through the 8 cm diameter outlet at
the back of the stove. The smoke outlet must be connected to
The pipe must be hermetically sealed.
The material used to seal and if necessary insulate the pipes,
must be resistant to high temperatures (high temperature silico-
The only horizontal section allowed may be up to 2 m long. It
A vertical section of at least 1.5m and an anti-wind terminal
The vertical duct can be internal or external. If the smoke chan-
nel is outside, it must be appropriately insulated.
must be suitable for solid fuel.
If it is wider than 150 mm in diameter it must be improved by
entering a pipe that has a suitable cross-section and is made of
-
the smoke duct must be accessible for inspection.
The chimney pots and smoke ducts connected to the solid fuel
appliances must be cleaned once a year (verify whether a speci-
Failure to regularly inspect and clean the stove increases the
Empty the pellet hopper; Contact specialist personnel before
reigniting the stove.
The stove is designed to work under any weather conditions.
In case of particular conditions, such as strong wind, the safety
system may be activated, which results in the stove being
extinguished. If this happens, do not operate the stove with
the safety devices disabled. If the problem persists, contact our
Technical Service Department. In this case, do not operate the
appliance while the safety devices are disabled. If the problem
persists, contact the Service Centre.
TYPICAL EXAMPLES
minimum height of 1.5 m and in any case above the height of the
roof gutter
CHIMNEY POT
The main characteristics are:
- an internal cross-section at the base, which is the same as that
- an outlet cross-section which is no smaller than twice that of
- its position must be high enough to catch the wind and avoid
downdraft areas in turbulent wind, it must be high enough to
catch the wind and avoid downdraft areas in turbulent wind.