Terminals "10 & 14". Normally closed contact. Connect, between these 2 terminals, any pulse generator (e.g. push-button, key selector,
etc..) which, by opening the contact, must command immediate stop of the beam and the de-activation of any automatic re-closure. To
resume the normal programmed cycle after this contact has been activated, use any pulse generator which commands the opening and/or
closing of the beam. The status of this input is signalled by LED "DL4".
If there are several pulse generators, they must be connected in series.
5.2.8. s
AFety devices
Terminals "10 & 15". Normally closed contact. Connect, to these terminals, any safety device (e.g. photocells) which, by opening the
contact, acts on beam motion. They can be active only during closure, or active in both closing and opening, according to the position of
dip-switch 6, see paragraph 6.
If the safety devices are not used, a connection must be made between terminal 4 and terminal 15.
If there are several safety devices, they must be connected in series.
Safety devices active at closure
If the safety devices are activated during closure, the control unit immediately reverses beam movement until opening is complete without
disabling - if selected - automatic re-closing of the beam.
Safety devices active at closure and opening:
In this case the safety devices are active on both beam movements. If the safety devices are activated during closure, the control unit
immediately reverses beam movement until opening is complete without disabling - if selected - automatic re-closing of the beam. If the
safety devices are activated during opening, the control unit immediately stops beam movement and keeps it stopped until the safety device
is reset (obstacle removed), and only then will the opening manoeuvre which had been started be resumed.
The status of this input is signalled by the LED located under the contact.

5.3 MOTOR CONNECTION

The automated system is supplied designed for right hand closure, with the motor connected to connector JP4. For left hand closure,
the motor must be connected to connector JP5.
To identify beam closing direction, look at the automated system from the side of the release device. If the beam has to descend on the
left of the automated system in order to close, left hand closure is involved, vice-versa, if the beam has to descend on the right of the
automated system in order to close, right hand closure is involved.
Two motors cannot be connected to the same control unit.
5.4. BATTERY KIT
A battery kit can be connected to the board - see price list - to make up for a possible power cut.
For correct positioning of the battery kit inside the motor body, refer to the instruction for the mechanical part.
The battery kit must be connected to connector JP2.
6 dip-switches are located on the control unit. They command the behaviour of the automated system and of the safety devices connected
to it. The behaviour of every dip-switch is summarised on the following table:
Automatic closing: Allows you to switch any automatic closing of the bar
Automatic closure enabled
Automatic closing deactivated
Admission OPEN / CLOSE: Allows you to select the input behavior OPEN / CLOSE
Open / Stop / Close / Stop / Open / ...
Open / Close / Open /....
Condominial Logic: Allows you to activate the pool. Enabling this feature during the opening operation of the bar, the control unit ignores
any commands OPEN or OPEN / CLOSE
Logic condominial activated
Logic condominial deactivated
Rod Open: This feature is described in the following paragraph
Function open rod activated
Function open auction deactivated
6. DIP-SWITCH ADJUSTMENT
E604
Pagina 1
Guide for the installer