  • MX

Idiomas disponibles

  • MEXICANO, página 64

5 Tank Priority

5.1

Systems with two tanks (Systems 2, 3, 9, 10, 13 and 17)

Priority
If the value of "dT" (T1 minus T2/T4) reaches the value required for charging, tanks 1 and 2 are
None
Tank 1
Tank 2
Tank 1
If T1>T2/T4 and T2>T2 max and T4>T4 max
5.2

Systems with three tanks (Systems 11, 14, 15 and 18)

Priority
If the value of "dT" (T1 minus T2/T3/T7) reaches the value required for charging, tanks 1/2/3 are
None
If T1>T2 and T2<T2 max (regardless of T3 and T4)
If T1<T2 and T2<T2 max and the value of "dT" (T1-T3/T7)
reaches the values required for charging, tanks 1/2/3 are
separately charged until the tanks reach the maximum
Tank 1
IF T1>T7 and T2>T2 max and T3>T3 max and T7<T7 max
IF T1>T2/T3/T7 and T2>T2 max and T3>T3 max and T7>T7
separately charged until the tanks reach the maximum temperature.
Priority for tank 1 (for Duplex)
Priority to tank 2 (for Duplex)
If T1>T2 and T2<T2 max (regardless of T4)
If T1<T2 and T2<T2 max and T1>T4 and
T4<T4 max
If T1>T4 and T2>T2 max and T4<T4 max
separately charged until the tanks reach the maximum temperature.
temperature.
If T1>T3 and T2>T2 max
If T1>T7 and T2>T2 max and T3<T3 max
max
Functions
For Multiplex systems 9, 10, 13 and 17 tank 1
Charge tank 2 synchronously
Priority charging time/Priority pause time
Functions
Priority charging time/priority pause time
15
always takes priority
Charge tank 1
Charge tank 2
Stop charging
Charge tank 1
Synchronously charge tank 2
Priority charging time
Priority pause time
Charge tank 2
Synchronously charge tank 3
Charge tank 3
Stop charging