1

Presentation and description

1.1

Product description

■ Expansion module (only in conjunction with the Duplex Basic double-loop solar control unit)
■ For multiple-loop solar and heating systems
■ Large display with backlight for graphical indication of schematic, operating status, temperatures output and energy yield. Simple,
menu-based operation with 4 keys
■ 18 standard systems for 1 to 4 tanks and 1 or 2 collector arrays, systems with plate heat
exchanger also selectable
■ Selectable functional blocks can be connected to the outputs (difference, thermostat, plate heat exchanger and timer), especially to
control individual solar and heating systems and additional functions
■ Two weather-compensating heating circuits with remote control, domestic hot water priority circuit and auto summer mode
■ 16 inputs and 10 outputs
■ 4 outputs (Triac), with either phase control for electronic speed control of standard solar and heating pump or with PWM signal for
speed controlled high-efficiency energy-saving pumps.
■ 6 outputs (relays) for standard solar and heating pumps
■ 2 inputs for VFS flow sensors for measuring flow rate and temperature and for system control, as well as energy balancing (no
wearing parts).
■ 2 inputs for RPS pressure sensors and for system control
■ Integrated, permanent storage of operating data, with graphical indication on display.
■ SD memory card slot: permanent, long-term recording for data logging of system parameters and operating data (temperatures,
pump status, operating time, output and energy yield). Detailed evaluation on a PC (system monitoring, system configuration, energy
yield for energy balancing).
Order SD card and software separately – SD Data log kit 1510327
■ Protective functions (overheating protection for collector and system, frost protection, pump exercise function)
■ Sensor auto check and alarm.
■ Energy saving mode (automatic display standby mode after 15 mins.)
1.2

Technical characteristics

Designation
Type
Item no.
Housing
Operating temperature
Protection class
Electrical connection
Total connected load Duplex
Total connected load Multiplex
Duplex fuse
Multiplex fuse
Dimensions Duplex
Dimensions Multiplex
Mounting Duplex
Mounting Multiplex
Menu languages
Operating modes
Sensors
Sensor monitoring
Protective functions
Multi-tank systems
Multiplex Advanced multiple-loop solar and heating control unit
VPM Multiplex
1510319
Plastic anthracite
0-50 °C
IP 42
230 VAC / 50 Hz
4.7 A / 230 VAC
5.8 A / 230 VAC
Pico fuse 5 A/250 V (5 x 20 mm)
Pico fuse 6.3 A/250 V (5 x 20 mm)
160 x 86 x 53
375 x 90 x 56
Wall mounting or installation in the TiSUN solar stations up to 50 m2
Wall mounting or installation in a distribution panel or protective casing
8 languages
Automatic, off or manual with test menu
Pt 1000
Automatic sensor testing (short-circuit and open-circuit) with fault display
Overheating protection for collector and system, recooling, frost protection, pump exercise
function
Tank priority circuit