Technical Data; Identification Code; Electrical Features; Installation - Scame ADVANCE-GRP Serie Instalación Uso Y Mantenimiento

Ocultar thumbs Ver también para ADVANCE-GRP Serie:
Tabla de contenido

Publicidad

ADVANCE-GRP[GD] Series

2. Technical data

2.1 Dimensional Drawings
Figure 1 - page 1
2.2 Type of Protections
ATEX / IECEx:
Ex db eb IIC T
(1)
Gb
Ex tb IIIC T80°C Db IP66
Tamb.
(2)
Tcable:
(3)
EAC Ex:
1Ex d e IIC T
Gb X
(1)
Ex tb IIIC T80°C Db X
IP66
Tamb.
(2)
Tcable:
(3)
(1)
Temperature Class for Gas according to the table 1.
Ambient temperature range according to the table 1 when different from –20°C to +40°C.
(2)
Tcable: 80°C for type 504.16... when maximum ambient temperature is +60°C.
(3)
Tcable: 85°C for type 504.32... when maximum ambient temperature is +60°C.
Tcable: 90°C for type 504.63... when maximum ambient temperature is +60°C.
Tcable: 85°C for type 504.125...
2.3 Example Marking Label ATEX / IECEx
Figure 2a - page 1
2.3.1 Example Marking Label EAC Ex
Figure 2b - page 2
2.4 Certificates
Atex Certificate: INERIS 15 ATEX 0017 X
IECEx Certificate: IECEx INE 15.0033 X
EAC Ex Certificate НАНИО ЦСВЭ № TC RU C-IT.AA87.B.00870
2.5 Ambient temperature range
table 1 - page 2.
2.6 Warning label
DO NOT OPEN WHEN
AN EXPLOSIVE ATMOSPHERE IS PRESENT 

3. Identification Code

The ADVANCE-GRP[GD] available part numbers types:
table 2 - page 2.

4. Electrical features

Switch Socket Type
Rated Voltage
400V
AC3
-
Category
AC22A
-
AC23A
-
Table 3
4.1 Cross Sectional Areas Conductors & Torque
SWITCH TERMINALS CONTACTS - TORQUE
Cross Sectional Areas Conductors
Switch Socket Type
Minimum
16A
4 mm²
32A
6 mm²
63A
16 mm²
125A
50 mm²
Table 4
4.1.1 Earth Terminals
EARTH TERMINALS CONTACTS - TORQUE
Type
Cross Sectional Areas Conductors
16/32A
10/16 mm²
63A
Weidmuller Ex e terminal - type WPE35 35mm²
125A
50/70mm² - CZ0513-180A - Switch-Earth Terminal
Table 5
4.2 Auxiliary contacts
In the sockets ADVANCE-GRP[GD] type 16A, 32A, and 63A can be install as optional 2 auxiliary
MP39683
16/32A
63A
500V
690V
400V
500V
690V
25A
-
-
50A
-
-
32A
-
-
63A
32A
-
-
-
63A
Tightening Torque -
Maximum
10 mm²
10 mm²
25 mm²
70 mm²
Tightening Torque - (Nm)
contacts maximum, on model type 125A is not possible to install auxiliary contacts.
They are optional accessories with ATEX / IECEx / EAC Ex separate certificates. Installation and
maintenance shall be done as prescribed by manufacturer documents. Creepage and clearance
distances shall comply with IEC EN 60079-7 / ГОСТ Р МЭК 60079-7-2012 at Table 1, current and
maximum dissipated power shall not exceed the maximum value allowed.
4.3 How to install Auxiliary Contact
Figure 3 - page 3
4.3.1 Electrical Parameters - Auxiliary Contact
The parameters relating to the safety , available only for ATEX certification, is not possible to mount
auxiliary contacts for IECEx certification.
For Russian Market the auxiliary contacts must be certified EAC Ex.
4.3.1.1 Switch type ZBWE-....
For ADVANCE-GRP[GD] 16/32A/63A
Maximum Supply Voltage: 415 V
Maximum Current: 4 A
Maximum Dissipation: 1W
Wiring by screw clamp 2x 1,5 mm ² or 1 x 2.5 mm ² with tip.
Torque: 0,8Nm à 1,2Nm max
4.3.1.2 Switch type M-053x
For ADVANCE-GRP[GD] 16/32A/63A
Electrical charateristics:
Contact block type M-0530 and M-0531
Rated operating voltage Ue... up to
Rated current Ie............... max
Rated operating voltage Ue... up to
Rated current Ie............... max
Rated operating voltage Ue... up to
Rated current Ie............... max
Conductors section
Schedule of limitations for components:
Rated service temperature range: from -40°C to +80°C.
4.3.2 ATEX Certification – Auxiliary Contact
Type
V max - I max
ZBWE-....
CZ0513-180A
690V
M-053x
125A
Table 6
125A
4.3.3 IECEx Certification – Auxiliary Contact
125A
Type
ZBWE-....
M-053x
(Nm)
Table 7
0.8

5. Installation

Installation shall be carried out by suitably-trained personnel in accordance with
2.5
the applicable code of practice (e.g. IEC EN 60079-14) and the provisions of the
3.5
national safety and accident prevention regulations and this instruction manual.
5.1 Safety Instructions
Use the switch only for its intended purpose. Incorrect or impermissible use or noncompliance with
these instructions invalidates our warranty provision. No changes to the switch impairing its explosion
protection are permitted. Fit and operate the switch only if it is clean and undamaged.
The contact element must be replaced after each short-circuit in the switch main
circuit. This is because the device is hermetically sealed and the state of the
1.2
switching contacts cannot be checked. Any damage can invalidate the Ex
protection.
3.5
5.2 Accessories
• Auxiliary Contacts type see topic 4.2.
• Earth-stud (stud, nuts and plain washer) made in brass, iron or in stainless steel AISI 316
• Cable-glands and blanking-plugs with separate certificates.
Detail of optional earth-stud: Figure 4 - page 4
Only approved and genuine SCAME accessories must be used.
7
Parameter
AC 15
400 V
500 V
690 V
Max 2,5 mm
Mode of
ATEX Certificate
protection
EX-TECH SOLUTION
415V – 4A
Ex db eb IIC Gb
INERIS 02 ATEX 9007U
CORTEM
400V – 4A
Ex d e IIC
CESI 09 ATEX 016 U
Mode of
V max - I max
protection
EX-TECH SOLUTION
415V – 4A
Ex db eb IIC Gb
CORTEM
400V – 4A
Ex d e IIC
Category of utilisation
DC 13
48 V
4 A
4 A
4 A
-
2 A
2
Max 2,5 mm
2
Ambient
Temperature
-50°C / +75°C
-40°C / +80°C
Ambient
IECEx Certificate
Temperature
IECEx INE 13.0063U
-50°C / +75°C
IECEx CES 11.0031U
-40°C / +80°C
ZP90904-4

Publicidad

Tabla de contenido
loading

Tabla de contenido