S19-672, S19-671
Installation S19-671
Step 1: Install eyewash
1. Remove the plastic dust plug from the bottom
of the yoke assembly and discard. Attach the
eyewash yoke assembly to the tank. Max. torque
150 In-Lbs.
2. Attach the pressure gauge to the adapter on
the pressure side of the tank with pipe sealant
(supplied by installer) as shown, page 7.
IMPORTANT: When attaching the pressure
gauge to the tank outlet, hold the adapter
(item 3) with a wrench to prevent stripping.
Failure to do so may damage the seal and
cause leakage. Max. torque 150 in-lbs.
Step 2: Fill tank and pressurize
1. If the tank is pressurized, relieve tank pressure by
pulling up on relief tank tab in center of cover until
pressure gauge reads "0."
IMPORTANT: DO NOT open cover until
pressure gauge reads "0"!
2. Open tank by pulling up on wire handle located on
top of the Quicklock cover. Push down, rotate and
remove. Fill container with 4 gallons of potable
water. Replace cover.
3. After filling the tank with water and before
pressurizing the unit, cycle the valve from the
closed to open and back to closed. Pressurize
tank to 90 psi by applying air pressure to the tank
valve located beneath the pressure gauge.
NOTE: Relief valve is designed to automatically vent at
100-130 psi to prevent the tank from overpressurizing.
Step 3: Flush tank
1. Discharge the water through the eyewash for at
least five minutes to flush the system.
2. Refill the tank and pressurize as explained in Step
2 outlined above.
NOTE: Let unit stand for one hour. If there is a
noticeable pressure drop, repressurize and let
stand for one hour. If problems persist, consult the
Troubleshooting guide found on page 5.
NOTE: This unit will provide 8 minutes of cleansing
action. Take the injured person immedi ately to a
normal emergency station for additional cleansing and
treatment.
4
4/14/09
8½"
(216mm)
Bradley Corporation • 215-321B Rev. N; ECM 09-05-0003
Installation
6"
(152mm)
27½"
(699mm)
35
5
⁄
"
8
(905mm)
25"
(635mm)