Front-Panel Indicators; Pumping Alarm Condition - On Primary Power - Liberty Pumps ProVore PDC-115 Manual De Instalación

Ocultar thumbs Ver también para ProVore PDC-115:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Front-Panel Indicators

The horn and LED indicators on the front panel are used to show various conditions of the controller. Each indicator is
described below.
Indicator
Indicator state
Power led
OFF
On constantly
Blinking
Horn disable
Blinking
LED
OFF
Alarm LED
OFF
On constantly
Blinking
Pump 1 LED
OFF
On constantly
Blinking
Pump 2 LED
OFF
On constantly
Blinking
Both pump 1 &
Blinking
Pump 2 LED
Horn
OFF
ON
Chirping
Pumping Alarm Condition – On Primary Power
The controller monitors a "pumping alarm condition" where a pump is called to run and the liquid level continues to rise
and goes above the Alarm Float switch. If a pumping alarm condition occurs three or more of the last five times a pump is
called to run, the pump indicator will blink indicating system components should be checked. Any of the following
conditions could cause a pumping alarm condition:
1) A pump fails to operate
2) The Alarm Float switch stays (mechanically stuck) in the closed (on, or up) position.
3) There is a problem (blocked or leak) in the out-flow plumbing
4) The water in-flow rate is greater than the pump-out rate
5) The Primary Float switch stays (mechanically stuck) in the open (off, or down) position.
A blinking light indicates a component failed and service is required. To assist the service technician the controller will
indicate which component has failed.
Blinking LED
Power light
Pump 1
Pump 2
Pump 1 and pump 2
Alarm light
Description
Power is off to the panel and the battery is dead
Primary power to the panel is ON
Primary power to the panel is OFF; the panel is on alarm backup power. Pumps will
NOT run. See Front-Panel indicators – On Alarm backup power.
Horn operation is DISABLED. The horn will NOT sound in an alarm condition.
Horn operation is ENABLED. The horn WILL sound in an alarm condition
There is no alarm condition
An alarm condition is active
The Alarm Float switch is not working properly
The pump is not being called to run
The pump IS being called to run
A pumping alarm condition occurred multiple times; see the section Pumping Alarm
Condition below
The pump is not being called to run
The pump IS being called to run
A pumping alarm condition occurred multiple times; see the section Pumping Alarm
Condition below
The primary float switch is not working properly.
No alarm condition is present, and the alarm backup battery is in good condition
An alarm condition is present
The voltage of the alarm backup battery is low and the battery should be replaced
No AC power, main breaker has tripped or power outage
Pump failed to operate; fuse tripped, jammed impeller, unplugged, short circuit...
Pump failed to operate; fuse tripped, jammed impeller, unplugged, short circuit...
Primary float switch; mechanically stuck open or tangled in an open condition.
Alarm float switch; mechanically stuck closed or tangled in a closed condition.
©Copyright 2013 Liberty Pumps Inc. All rights reserved
Related problem
4

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Provore pdc-230

Tabla de contenido