ELECTRICAL WIRING
The indoor and CXS H units must be connected electrically
to each other as shown in the wiring diagrams.
To protect the unit against short circuits fit an omnipolar ther-
momagnetic switch 250V (IM1) (with power 1~ 230V 50Hz
) on the power line, with a minimum contact opening distance
of 3mm (TAB. F).
The connection terminals of the CXS-H unit are connected
in the electrical box that can accessed by removing the pla-
stic plug at the side.
For connections between the units, the values of the cable
ELECTRICAL DATA
IM
[A]
SECT. A[mm 2 ]
WIRING DIAGRAMS
KEY
CC
= Compressor contactor
CMCP = Running compressor capacitor
CMV
= Running fan capacitor
CP
= Compressor
MV
= Fan Motor
PT
= Motor protection
RPF
= Phase sequence control relay
RT
= Thermal relay
VI
= Cycle inversion valve
IM
= Line switch
L
= Power phase
N
= Power neutral
CXS 1207 H
Wiring diagrams subject to change; check the wiring diagram provided with the unit.
24
CXS 1207 H
15
2
Standard ventilation
connection (3)
1 2 3
N
NE 1,5
VIC
BL
BI
NE 1,5
CM
NE 1,5
PT
NE 1,5
S R C
M
1
CP
cross sections and the IM switch, see the "Wiring Diagram"
section.
During installation it is possible to select two head levels
(standard or maximum head) connecting the power supply
of the fan motor to clamps 3 or 4.
PE
= Earthing connection
Connections made on-site
Components not supplied
NE
= Black
BI
= White
BL
= Blue
NE
= Black
RO
= Red
MA
= Brown
GR
= Grey
VI
= Violet
Connection for ventilation with
(4) Maximum head
4
BL
NE
RO
BI
CM
M
1
MV
dis. 4843700_01