Technical Data; Kit Includes - Aspen Pumps mini lime Serie Manual De Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Technical Data:

POWER SUPPLY:
Mini Lime: 120V AC 0.16A 13.5W 60Hz or
230V AC 0.10A 15W 60Hz
Maxi Lime: 120V AC 0.23A 18W 60Hz or
230V AC 0.10A 15W 60Hz
3A volt-free Alarm wires, N/O N/C contacts rated
@ 5A inductive at 120V or 230V AC.
Mini Lime: Continuously rated
Maxi Lime: Non-continuously rated -
operating time: 10 mins on / 5 mins off
Mini Lime: Class I appliance
Maxi Lime: Class II appliance
Hall effect electronic water level sensors
Thermally protected
Maximum water temperature: 104ºF

Kit includes:

*
*
4
3
3
2
7
2
5
1a
1b
6
Operating levels:
The float inside the reservoir operates at 3 different
heights which are illustrated in the diagram below.
NOTE: To stop the pump running, the float must rest in
the lowest position, on the bottom of the reservoir.
3 /
" – Pump is off.
8
3 /
" – Pump operates.
4
1" – Safety switch operates, switches off AC unit and
activates optional alarm.
1
®
ETL
listed
CAPACITY:
Mini Lime: 3.7 GPH @ zero head, 0.8 GPH @26ft head
Maxi Lime: 5.8 GPH @ zero head, 0.8 GPH @49ft head
MAXIMUM RECOMMENDED HEAD:
Mini Lime: 26ft Maxi Lime: 49ft
1 /
Discharge tube
" i.d
4
Gravity inlet
SOUND LEVEL:
Mini Lime: 23dB(A) Maxi Lime: 35dB(A)
Mini Lime handles minisplits up to 30,000 btu/hr
Maxi Lime handles minisplits up to 60,000 btu/hr
Fully potted
Check all components are present before starting installation.
1a. MINI LIME: Pump/cable assembly with 6"
3 /
breather tube and 5 ft x
" i.d. green discharge
16
1 /
3 /
tube fitted with
" –
" reducing connector.
4
16
1b. MAXI LIME: Pump/cable assembly with 6"
1 /
breather tube and 5 ft x
" i.d. discharge tube fitted
4
1 /
with
" double barb connector (plus 31" insulation).
4
2. Elbow
3. 31" lineset cover
4. Ceiling plate
1 /
5. 20"
" i.d. green connector tube
2
6. Evaporator flashing (Available later in 2006)
7. 2 Connecting couplers for Aspen Slimline series.
(Model ASP – ML115 & ASP – ML 230 only)
8. Wallplugs and screws
9. Installation manual
*
NOTE: You will need a further length of
discharge tubing to reach an appropriate drain point.
NOTE: For Model ASP – ML115 & ASP – ML 230, Aspen
Slimline series, additional couplers and 31" lengths of
Slimline lineset cover are available as spare parts.
3
1"
"
3
/4
"
/8
Typical Performance:
45
MINI LIME
40
35
30
WE DO NOT RECOMMEND
25
20
15
10
5
0
0
1
US GALLONS PER HOUR
DO NOT RUN THESE PUMPS DRY. SERIOUS DAMAGE WILL OCCUR AND INVALIDATE WARRANTY.
Product Safety:
1 /
" i.d.
4
CAUTION: The Mini and Maxi Lime Pumps have been evaluated for use with water only.
WARNING: Risk of electric shock. This pump has not been investigated for use in swimming
1 /
" i.d.
4
pool or marine areas.
The means for isolation must be incorporated in the fixed wiring in accordance with wiring regulations.
Ensure the Pump is disconnected from the Mains supply before carrying out
any adjustments or servicing.
The supply cord cannot be replaced. If the cord is damaged the appliance should be scrapped.
Always ensure the metal magnet in the float is facing upwards.
The Pump is ideal for most working and living environments. It is not recommended
where the environment is oily or particularly dusty.
Acceptable for indoor use only.
Non-submersible pump.
1 /
" i.d.
4
Consignes de sécurité:
ATTENTION : Les pompes Mini et Maxi VERTE sont conçues pour pomper uniquement de l'eau.
AVERTISSEMENT : Risque de décharge électrique. Cette pompe n'a pas été étudiée pour
l'usage dans une piscine, un aquarium ou en fonctionnement immergé.
80
70
60
70
60
OPERATING ABOVE
50
26 ft HEAD
40
30
20
10
0
0
1
2
2
3
4
US GALLONS PER HOUR
MAXI LIME
WE DO NOT RECOMMEND
OPERATING ABOVE
49 ft HEAD
3
4
5
6
7
2

Publicidad

Tabla de contenido