ND 5119-5 61-065 Vol-Con Ins
Applications:
• Locating Blown Fuses
With power on: Place
tester across the "source"
side of one fuse and the
load side of an adjoining
fuse. If no voltage is
indicated, the fuse next to
the load side prod is blown.
If voltage is indicated, the fuse next to the
load side prod is OK. Repeat the same test
with the prods on the opposite side of the
same two fuses to check the other fuse.
On a three phase circuit, repeat the same test
as above. An indication of no voltage or
lower than normal line voltage indicates the
blown fuse.
• Testing for 25 to 60 Cycle Frequency
Place tester between each side of AC line. A
low frequency hum and slow vibrations indi-
cate 25 cycle current. 60 cycle current is
indicated by a higher frequency hum and
more rapid vibrations.
Test Lead Replacement:
• Replace leads only with IDEAL test leads
below.
• # 61-070 Standard Test Leads with
Shielded Probe Tips
• # 61-072 Resistor-fused Test Leads with
Shielded Probe Tips. Each probe tip con-
tains a special, current-limiting resistor
which acts like a fuse to limit short-circuit
current and prevents dangerous arcing
during a shorted condition. The resistors
are rated to 140Ω +/- 10%. Fusing cur-
rent is 1A at 125V. Fusing time is 30-
60ms at 125V, without causing dangerous
conditions during opening of the fuse ele-
ment. Leads need to be replaced when
fuse has opened.
2/19/07
9:18 AM
Page 3
Maintenance:
• Clean the case with a damp cloth and mild
detergent. Do not use abrasives or solvents.
Service, and Replacement Parts:
For replacement parts or to inquire about
service information contact
IDEAL INDUSTRIES, INC.
Attn: Repair Department
1000 Park Avenue
Sycamore, IL 60178
Technical Support: 1-877-201-9005 or visit
our website at www.testersandmeters.com.
Specifications:
VAC Ranges: 120V, 240V, 480V, 600V AC.
VAC Accuracy: Relative indication only
VDC Ranges: 120V, 240V, 600V DC
VDC Accuracy: Relative indication only
Neon bulb lights from 100-600V AC/DC
Operating Frequency: 25-60 Hz
Input Impedance: Low
Overload protection: 1000VDC/750VAC rms.
Operating Environment: 32° F to 122° F
(<70% humidity)
Storage Temp.: -4° F to 140° F
(<80% humidity)
Accessories included: Test Leads, operating
instructions
Dimensions: 7.2" (H), 2.4" (W), 1.5" (D)
Weight: 8.0 oz
Safety:
R
3
4