10 Anexo
Codificación del bit de estado para el valor de salida PA
Código
Descripción según la norma
Profibus
de es-
tado
0x00
bad - non-specific
0x04
bad - configuration error
0x0C
bad - sensor failure
0x10
bad - sensor failure
0 x 1f
bad - out of service constant
0 x 44
uncertain - last unstable value
0 x 48
uncertain substitute set
0 x 4c
uncertain - initial value
0 x 51
uncertain - sensor; conversion
not accurate - low limited
0 x 52
uncertain - sensor; conversion
not accurate - high limited
good (non-cascade) - OK
0 x 80
0 x 84
good (non-cascade) - active
block alarm
0 x 89
good (non-cascade) - active ad-
visory alarm - low limited
0 x 8a
good (non-cascade) - active ad-
visory alarm - high limited
0 x 8d
good (non-cascade) - active cri-
tical alarm - low limited
0 x 8e
good (non-cascade) - active cri-
tical alarm - high limited
72
Causa posible
Actualización Flash activa
l Error de ajuste
l Error de configuración en la escala PV (PV-Span too small)
l Falta de concordancia de la unidad de medida
l Error en la tabla de linealización
l Error de hardware
l Error del transductor
l Error de pulso de fuga
l Error de disparo
l Error de ganancia del valor de medición
l Error de medición de temperatura
Modo „Out Of Service" conectado
Valor de sustitución Failsafe (Failsafe-Mode = "Last value" y valor
de medición valido desde la conexión)
l Conectar simulación
l Valor de sustitución Failsafe (Failsafe-Mode = „Fsafe value")
Valor de sustitución Failsafe (Failsafe-Mode = "Last valid value" y
todavía ningún valor de medición valido desde la conexión)
Valor del sensor < limite inferior
Valor del sensor > limite superior
OK
Static revision (FB, TB) changed (activa durante 10 seg , después
de la escritura del parámetro de categoría estática)
Lo-Alarm
Hi-Alarm
Lo-Lo-Alarm
Hi-Hi-Alarm
VEGABAR 67 • Profibus PA