Atsumi Electric Tri Watcher SIR10SA Manual De Instalación página 7

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7. SETTING SWITCHES
Make the switch settings after removing the small cover from the main device.
Vol.1
ON
OFF
1. Detection sensitivity selection function
(Sensitivity volume)
The detection sensitivity of the detector can be adjusted.
Range: 50% - 100% - 150%
The default detection sensitivity is 100%.
Operation : When set to 100%, the detection sensitivity when
walking at 1 m/s in a 35°C environment is 1.5°C.
2. Pulse count function
Detection operation is performed by a preset number of
signal inputs.
Function selection : Set the setting switches to select one
of the four types below.
Switch 1
On
(Default
Off
setting)
On
Off
Operation : The number of signal inputs within 10 seconds
are countered, and if they reach to a preset
count, the detection operation is performed.
When 10 seconds elapses from the last signal
input, the count value is reset.
Normally, when a person passes through a zone,
one or two signal inputs are obtained, but if the
temperature difference is small between the
person and the background of the floor or wall,
only one signal is obtained. Therefore, keep this
point in mind when making the setting.
Setting volume 1 ..................Sensitivity
Setting switches 1 and 2 ......Pulse count (Default: OFF, ON)
Setting switch 3 ...................LED indicator (Default: ON)
Setting switch 4 ................... LED precaution and Anti-Masking LED
(Setting switches 1 and 2)
Switch 2
No. of signals
On
1
On
2
Off
3
Off
4
indicator (Default: OFF)
3. LED indicator selection function
(Setting switch 3)
On : Alarm LEDs 1 and 2 (red) are normally off, and turn
on at detection. (Default setting)
Off : Alarm LEDs 1 and 2 (red) are normally off, and do
not turn on at detection.
4. LED precaution and Anti-Masking LED
indicator
(Setting switch 4)
In normal conditions, the alarm LEDs 1 and 2 are
alternately turned on. (once every 2.5 seconds)
Upon detection of Anti-Masking, the alarm LEDs 1 and 2
start fl ashing simultaneously. (5 times a second)
The alarm LEDs fl ash at different intervals between when
operation is in normal conditions and when Anti-Masking
is detected.
On : The LED alarm is used. This function can be used
even though LED indicator selection is off.
Off : The LED alarm is not used. (Default setting)
7