The SA03 control unit with microcontroller can be used with motors having a power not exceeding
750W.
Attention: Whenever the power supply is restored and a Step-by-Step command is given to the control
unit, you must wait until the automation has completed the whole interval defined by the work time (wait
until the blinker switches off).
Installation instructions.
a) The electrical installation and functioning logic must comply with current standards.
b) Keep the power cables (for the motor and power supply) away from the control cables (buttons,
photocells, radio). To avoid interference use two separate sheaths (see EN 60204-1 15.1.3).
c) Check all the connections again before supplying voltage.
d) Check that the Dip-Switch settings are as required.
e) The Normally Closed contacts which are not in use should be short circuited.
f) If the direction of the motor rotation is not correct, invert the "OPEN" - "CLOSE" wires of the motor.
Input/Output functions
(1)
Antenna Signal
(2)
Antenna Shield
(3,8)
SCA= Indicator lamp, Open gate
(4)
P.P.= Input, Step-by-Step push-button (N.O. contact).
(5)
Stop= Input, Stop push-button (N.C. contact).
(6)
FTC= Input, photocell receiver (N.C. contact).
(7)
+V= Common, all control inputs.
(8,9)
OUT24VAC= Output, 24Vac auxiliary power supply (100mA max.).
(10,11)
ELS.= Connection to 12V Electric lock
(12,13,14) To secondary of the Capacitor
(15,16,17) To primary of the Capacitor
(18,19)
INPUT 230VAC= Control unit power supply, 230Vac, 50Hz (keep to phase/neutral).
(20,21)
Lamp= Flashing light
(22,23,24) APRE/CHIUDE/COM= To relevant terminals of Motor 2, at 230Vac, 50Hz.
It is mandatory to connect the Ground wire (yellow/green) on the motor frame.
(24,25,26) COM/CHIUDE/APRE= To respective terminals (Com, Close, Open) of Motor 1 at 230Vac, 50Hz.
It is mandatory to connect the Ground wire (yellow/green) on the motor frame.
(27,28)
2nd. CH.= Clean contact second channel radio card.
(29)
Ped.= Pedestrian button input (N.O. contact).
The control unit is equipped with a built-in radio module for the reception of both fixed code and vari-
able code remote controls at a frequency of 433.92MHz.
To use a remote control its data should be stored in the unit memory. This procedure is shown hereun-
der. The unit is able to memorize up to 14 different codes.
Dip-switch functions
DSW1= The operation of the "Step-by-Step button" and the remote control can be selected with this
Dip-Switch.
Off= "OPEN" - "STOP" - "CLOSE" functioning
On= "OPEN" - "CLOSE" - "OPEN" functioning.
DSW2= This enables or disables the automatic closure.
Off= Automatic closure disabled
On= Automatic closure enabled
DSW3= It enables or disables the multi-flat function.
Off= Multi-flat function disabled
On= Multi-flat function enabled
DSW4= It enables or disables the forewarning flashing light.
Off= Forewarning flashing disabled
On= Forewarning flashing enabled
6
SA03 Control unit with microcontroller