EMERGENCY EXIT DEVICES INSTALLATION ACCORDING TO EN 179

The following locks and handles are approved to be installed together in an emergency exit
door. Strike plate EA321, EA322, EA323, EA324, EA325, EA326, EA327, EA328, EA329,
EA330, EA331, EA332 must be used in the installation.
Profi le door locks
EL420
e.g. ABLOY® INOXI
EL422
3-19/013/120 PZ+BL
Wooden and metal
door locks
EL520
e.g. ABLOY® INOXI
EL522
3-19/012/120 PZ+BL
Functional check after installation:
Emergency exit (active) side and functional sensitivity tests:
- Use the handle of exit side.
- In the profi le door locks the force of handle is about 15 N (approximately 1.5 kg weight at a
100 mm distance from the pivot of the handle opens the lock).
- In the wooden door locks the force of handle is about 15 N (approximately 1.5 kg weight
at a 100 mm distance from the pivot of the handle opens the lock). According to EN 179 the
force of handle must be less than 70 N.
- Close the door slowly and check that the lock deadlocks.
- Check that the bolts slide freely into the strike plate.
!
The safety features of this product are essential to its compliance with EN 179. No modifi ca-
tion of any kind, other than those described in these instrictions, are permitted.

PANIC EXIT DEVICES INSTALLATION ACCORDING TO EN 1125

The following locks and push bars are approved to be installed together on the panic exit door.
Strike plate EA321, EA322, EA323, EA324, EA325, EA326, EA327, EA328, EA329, EA330,
EA331, EA332 must be used in the installation.
Profi le door locks
EL420
EL422
Wooden and
metal door locks
EL520
EL522
Functional check after installation:
Panic exit (active) side and functional sensitivity tests:
- Push the push bar towards the door on the exit side.
- Force to open the lock by pushing the bar is about 60 N (approximately 6kg). According
to EN 1125 it must be less than 80 N.
- Close the door slowly and check that the lock deadlocks.
- Check that the bolts slide freely into the strike plate.
Note! The length ot the push bar must be at least 60 % of the width of the door.
!
The safety features of this product are essential to its compliance with EN 1125. No modifi -
cation of any kind, other than those described in these instrictions, are permitted.
Recommended distance from a fl oor to a handle or to a push bar is between
900mm - 1100mm.
Lubricate the bolts of the lock case at least once a year. Use vaseline type lubrication.
Note! Abloy Oy will not be liable for products in case these instructions are not followed.
6
ABLOY®
IKON
DO 20.33.01
DO 20.15.02
DO 20.33.02
e.g. S6B8
ABLOY®
IKON
DO 20.33.01
DO 20.15.02
DO 20.33.02
e.g. S4K6
effeff
DO 30.04
8000-00-1100 (-), 8000-10-1100 (PZ)
8000-00-1100 (-), 8000-11-1100 (RZ)
effeff
DO 30.04
8000-00-1100 (-), 8000-20-1100 (PZ)
8000-00-1100 (-), 8000-21-1100 (RZ)
R
FSB
DO 20.03.01,
DO 20.03.02
1016, 1023, 1056, 1070, 1080,
1088, 1090, 1117, 1118, 1119,
1137, 1146, 1155, 1160, 1161,
1162, 1177, 1178, 1191, 0612,
0616, 0617, 0619, 0625, 0627,
0628, 0646, 0662, 0665, 0680,
0681, 0682, 0688
JPM
DO 30.05
NORMA
990000-XX-0A, 990100-XX-0A,
990001-XX-0A, 990101-XX-0A,
991000-XX-0A, 991100-XX-0A,
991001-XX-0A, 991101-XX-0A
HEWI
SAPEX
DO 20.13.01,
DO 20.32.01
DO 20.13.02
DO 20.32.02
111, 111.23,
e.g. 60-0719
114.23GK,
131, 132, 111X,
SAPEX
113X, 114X, 161X,
DO 20.32.01
163X, 171X, 112X,
DO 20.32.02
165X, 166X
e.g. 60-0119
TESA
DO 30.06
UNIVERSAL
SERIE
19709G9xx