Installation
5.3
Electrical connection (Qualified specialist)
WARNING
Risk of electric shock due to incomplete assembly!
Only apply power when the housing is closed with the
transparent lid.
WARNING
Risk of electric shock due to incorrect connections!
Electrical connections must always be carried out by
authorised specialists.
Observe VDE and utility company regulations.
Install pumps for swimming pools and their protection
according to DIN VDE 0100-702.
Observe DIN EN 60730 part 1.
Install a disconnecting device with at least a 3 mm contact
gap per pole to interrupt the power supply.
Protect power supply with a ground fault circuit interrupter,
nominal residual current I
Only use suitable pipe types according to regional
regulations.
Adjust minimum diameter of the electrical pipes to
accommodate the motor output and pipe length.
If hazardous situations can occur, provide an emergency off
switch according to DIN EN 809. The builder/operator must
make a decision according to this standard.
Connection by customer:
– Fuse protection 1 phase 230 V/3 phase 400 V safety fuse
10 A time delay
– Rated short circuit breaking capacity I
Mains power supply (L,N) 230 V, 50/60 Hz (continuous
voltage)
Connections may not be reversed.
32 EN
≤ 30 mA.
FN
CN
≤ 6 kA
04|2019