Datos técnicos
7.1 Todos los modelos
Tipo de protección 6DR5ayb-*cdef-g*Ah-Zjjj
Para c = G,
● a = 0, 2, 5, 6 y b = 1, 2, 3, 5, 6
● a = 1 y b = 3
Para c = K y b = 1, 2, 3, 5, 6
● a = 0, 2, 5, 6 y b = 1, 2, 3, 5, 6
● a = 1 y b = 3
External Position Transmitter:
● 6DR4004-1ES
● 6DR4004-2ES
● 6DR4004-3ES
● 6DR4004-4ES
7.1.5.3
Rangos de temperatura ambiente máximos permitidos
Posicionador y módulos opcionales
Posicionadores
● 6DR5ayb-0cdef-g*Ah-Z jjj
● 6DR5ayb-0cdef-g*Ah-Z M40
● 6DR5ayb-0cdef-g*Ah-Z jjj
para a = 0, 1, 2 y f = 0, 2
● 6DR5ayb-0cdef-g*Ah-Z M40
para a = 0, 1, 2 y f = 0, 2
Módulos opcionales
● Non Contacting Sensor (NCS)
6DR4004-6N
● External Position Transmitter (Potentiometer)
6DR4004-1ES
● External Position Transmitter (NCS)
6DR4004-2ES
● External Position Transmitter (NCS, ILS)
6DR4004-3ES
● External Position Transmitter (NCS, MLS)
6DR4004-4ES
66
Marcado Ex
ATEX 205947X
IECEx TUN 17.0023X
II 3 G Ex ec IIC T6/T4 Gc
II 2 G Ex ia IIC T6/T4 Gb
II 3 G Ex ic IIC T6/T4 Gc
II 2 D Ex ia IIIC T130°C Db
II 2 D Ex tb IIIC T100°C Db
II 3 G Ex ec IIC T6/T4 Gc
Clase de temperatura T4
-30°C ≤Ta ≤ +80°C
-40°C ≤Ta ≤ +80°C
-30°C ≤Ta ≤ +80°C
-40°C ≤Ta ≤ +80°C
-40 °C ≤Ta ≤ +90 °C
-40 °C ≤Ta ≤ +90 °C
-40 °C ≤Ta ≤ +90 °C
Instrucciones de servicio resumidas, 09/2019, A5E03436620-AE
Marcado Ex
FM 17US0053X
CSA 18CA70166848X
Cl I Zn 2 AEx nA IIC Gc
Cl I Zn 2 Ex nA IIC Gc
NI Cl I Div 2 Gp A-D
Cl I Zn 1 AEx ib IIC Gb
Cl I Zn 1 Ex ib IIC Gb
Zn 21 AEx ib IIIC, T130°C Db
Zn 21 Ex ib IIIC, T130°C Db
IS Cl I, II, III Div 1 Gp A-G
Cl I Zn 2 AEx nA IIC Gc
Cl I Zn 2 Ex nA IIC Gc
NI Cl I Div 2 Gp A-D
Zn 21 AEx tb IIIC T100°C Db
Zn 21 Ex tb IIIC T100°C Db
DIP Cl II, III Div 1 Gp E-G
Clase de temperatura T6
-30°C ≤Ta ≤ +50°C
-40°C ≤Ta ≤ +50°C
-30°C ≤Ta ≤ +60°C
-40°C ≤Ta ≤ +60°C
-40 °C ≤Ta ≤ +70 °C
-40 °C ≤Ta ≤ +60 °C
-40 °C ≤Ta ≤ +50 °C
SIPART PS2 (6DR5...)