Connection Of Battery Cables - Victron energy MultiPlus 12/5000/200-100 230V Manual Del Usuario

Ocultar thumbs Ver también para MultiPlus 12/5000/200-100 230V:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

4. INSTALLATION
This product may only be installed by a qualified electrical engineer.
4.1 Location
The product must be installed in a dry and w ell-ventilated area, as close as possible to the batteries. There should be a clear space of at
least 10 cm around the appliance for cooling.
Excessively high ambient temperature w ill result in the follow ing:
- Reduced service life.
- Reduced charging current.
- Reduced peak capacity, or shutdow n of the inverter.
- Never position the appliance directly above the batteries.
The MultiPlus is suitable for w all mounting. For mounting purposes, a hook and tw o holes are provided at the back of the casing (see
appendix G). The device can be fitted either horizontally or vertically. For optimal cooling, vertical fitting is preferred.
The interior of the product must remain accessible after installation.
Try and keep the distance betw een the product and the battery to a minimum in order to minimize cable voltage losses.
For safety purposes, this product should be installed in a heat-resistant
environment. You should prevent the presence of e.g. chemicals, synthetic
components, curtains or other textiles, etc., in the immediate vicinity.

4.2 Connection of battery cables

In order to utilize the full capacity of the product, batteries w ith sufficient capacity and battery cables with sufficient cross section should
be used. See table.
Recommended battery capacity (Ah)
Recommended DC fuse
Recommended cross section (mm
per + and - connection terminal
0 – 5 m
5 – 10 m
* '2x' means tw o positive and tw o negative cables.
Remark: Internal resistance is the important factor w hen working with low capacity batteries. Please consult your supplier or the relevant
sections of our book "Energy Unlimited", dow nloadable from our w ebsite.
Procedure
Proceed as follow s to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
- Undo the four screws at the front of the enclosure and remove the front panel.
- Connect the battery cables: see Appendix A.
- Tighten the nuts w ell for minimal contact resistance.
8
12/5000/200
24/5000/120
800–4200
400–1400
750A
400A
2
)
2
2x 90 mm
2x 50 mm
2x 90 mm
48/5000/70
200–800
200A
2
2
1x 70 mm
2
2
2x 70 mm

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Multiplus 24/5000/120-100 230vMultiplus 48/5000/70-100 230v

Tabla de contenido