5.5 Configuration with DIP switches
A number of settings can be changed using DIP sw itches (see appendix A, position M).
This is done as follow s:
Turn the MultiPlus on, preferably unloaded en w ithout AC voltage on the inputs. The Multi w ill then operate in inverter mode.
Step 1: Setting the DIP sw itches for:
- the required current limitation of the AC input.
- AES (Automatic Economy Sw itch)
- limitation of the charging current.
- selection of stand-alone, parallel or 3-phase operation.
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of the DIP
sw itches, see appendix A, position K). You can now re-use the DIP sw itches to apply the remaining settings (step 2).
Step 2: other settings
To store the settings after the required values have been set: press the 'Dow n' button for 2 seconds (lower button to the right of the DIP
sw itches). You can now leave the DIP sw itches in the selected positions, so that the 'other settings' can alw ays be recovered.
Rem arks:
- The DIP sw itch functions are described in 'top to bottom' order. Since the uppermost DIP sw itch has the highest number (8),
descriptions start with the switch numbered 8.
- In parallel mode or 3-phase mode, not all devices require all settings to be made (see section 5.5.1.4).
For parallel or 3-phase mode, read the w hole setting procedure and make a note of the required DIP sw itch settings before actually
implementing them.
5.5.1 Step 1

5.5.1.1 Current lim itation AC input (default: 50A)

If the current demand (Multi load + battery charger) threatens to exceed the set current, the MultiPlus w ill first reduce its charging
current (Pow erControl), and subsequently supply additional pow er from the battery (Pow erAssist), if needed.
The AC input current limit can be set to eight different values by means of DIP sw itches.
With a Multi Control Panel, a variable current limit can be set for the AC input.
Procedure
The AC input current limit can be set using DIP sw itches ds8, ds7 and ds6 (default setting: 50A).
Procedure: set the DIP sw itches to the required value:
ds8 ds7 ds6
off off off = 6,3A (1.4kVA at 230V)
off off on = 10A (2.3kVA at 230V)
off on off = 12A (2.8kVA at 230V)
off on on = 16A (3.7kVA at 230V)
on
off off = 20A (4.6kVA at 230V)
on
off on = 25A (5.7kVA at 230V)
on
on off = 30A (6.9kVA at 230V)
on
on on = 50A (11.5kVA at 230V)
Rem ark:
Manufacturer-specified continuous power ratings for small generators are sometimes inclined to be rather
optim istic. In that case, the current limit should be set to a m uch lower value than w ould otherwise be required on
the basis of m anufacturer-specified data.
5.5.1.2 AES (Automatic Economy Sw itch)
Procedure: set ds5 to the required value:
ds5
off = AES off
on = AES on
15