DIP sw itches ds2 and ds1 are reserved for the selection of stand-alone, parallel or
3-phase operation
Stand-alone operation
Step 1: Setting ds2 and ds1 for stand-alone operation
DS-8 AC input
Set as desired
DS-7 AC input
Set as desired
DS-6 AC input
Set as desired
DS-5 AES
Set as desired
DS-4 Charging current Set as desired
DS-3 Charging current Set as desired
DS-2 Stand-alone operation
DS-1 Stand-alone operation
Examples of DIP sw itch settings for stand-alone mode are given below .
Example 1 show s the factory setting (since factory settings are entered by computer, all DIP sw itches of a new product are set to 'off'
and do not reflect the actual settings in the microprocessor).
Four exam ples of stand-alone settings:
DS-8 AC input
on
DS-7 AC input
on
DS-6 AC input
on
DS-5 AES
of f
DS-4 Ch. current
on
DS-3 Ch. current
of f
DS-2 St.-alone mode
of f
DS-1 St.-alone mode
of f
Step1, stand-alone
Step1, stand-alone
Example 1 (factory setting):
Example 2:
8, 7, 6 AC-in: 50A
8, 7, 6 AC-in: 50A
5 AES: of f
5 AES: of f
4, 3 Charging current: 75%
4, 3 Charge: 100%
2, 1 Stand-alone mode
2, 1 Stand-alone
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of the DIP
sw itches, see appendix A, position K). The overload and low-battery LED's w ill flash to indicate acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe place.
You can now re-use the DIP sw itches to apply the remaining settings (step 2).
of f
of f
DS-8
on
DS-8
DS-7
on
DS-7
on
DS-6
on
DS-6
on
DS-5
of f
DS-5
DS-4
on
DS-4
on
DS-3
on
DS-3
on
DS-2
of f
DS-2
DS-1
of f
DS-1
Step1, stand-alone
Example 3:
8, 7, 6 AC-in: 16A
5 AES: of f
4, 3 Charge: 100%
2, 1 Stand-alone
of f
DS-8
on
DS-7
on
DS-6
of f
of f
DS-5
on
DS-4
of f
DS-3
on
of f
DS-2
of f
of f
DS-1
of f
Step1, stand-alone
Example 4:
8, 7, 6 AC-in: 30A
5 AES: on
4, 3 Charge: 50%
2, 1 Stand-alone